IF08CZ10 April, 2019
- 37 -
Analog Output
General-purpose Analog Output
Three channels (AOUT1, 2, and 3) are provided as general-purpose, 10VDC analog output from the
XIO brd.. These outputs are directly output from the control brd.. The device reading these signals must be
isolated. To insure this, it is recommended that signal isolators be used. The output can be selected from a
list shown in the parameter setting manual by using the parameters AOUT1-3_CODE. They may also be
set to any function in the drive by the use of the parameters AOUT1-3_OP_AS, AOUT1-3_OP_GS, and
AOUT1-3_OP_OS. When using the optional settings, care must be taken to set the output up so that the
output signal does not exceed 10VDC. Exceeding this value will cause overflow problems.
Additional Analog Outputs
Six channels (D/A 1 to D/A 5 and Amp A) are provided as additional analog outputs. These outputs
are wired out to terminal block TB-AO. Channel A provides direct current feedback from the U-phase Hall
CT. The other five channels are programmable 10VDC outputs. The data to be output, the gain, and the
offset, can be set from the display/keypad or a personal computer by use of parameters DA1-5_AS (Analog
Signal), DA1-5_GS (Signal Gain), and DA1-5_OS (Offset).
Summary of Contents for T300MTX
Page 19: ...IF08CZ10 April 2019 xix This page intentionally left blank ...
Page 62: ...IF08CZ10 April 2019 40 CIRCUIT OPERATION cont d 6600V configuration ...
Page 78: ...IF08CZ10 April 2019 56 DRIVE INSTALLATION DRAWINGS Frame 0 drive lifting and assembly ...
Page 106: ...IF08CZ10 April 2019 84 DRIVE INSTALLATION DRAWINGS cont d Frame A2 drive lifting and assembly ...
Page 109: ...IF08CZ10 April 2019 87 DRIVE INSTALLATION DRAWINGS cont d Frame B2 drive lifting and assembly ...
Page 111: ...IF08CZ10 April 2019 89 DRIVE INSTALLATION DRAWINGS cont d Frame D2 drive lifting and assembly ...
Page 116: ...IF08CZ10 April 2019 94 DRIVE INSTALLATION DRAWINGS cont d Frame A4 drive lifting and assembly ...