4. Configuration File
4.2.5 Tag setting
The tag setting specifies the tag name, corresponding register/device, update cycle, and data
type.
Two types of designation are available. These are the individual address designation (T) and the
continuous address designation (TA).
When the individual address designation is used, up to 32 tags can be used for one PLC per
one update cycle. On the other hand, when the continuous address designation is used, up to
248 tags can be used for one PLC per one update cycle.
Either individual or continuous designation can be used for one PLC per one update cycle.
The setting details and the column order is as follows.
Individual address designation:
Setting ID
T
Tag name
Any name (within 13 characters)
Register/device address
PLC's register/device address
Allowable types are X, Y, Z, L, R, S, XW, YW, W, LW,
RW, SW, T, C, D, F, T., or C. (18 types)
Allowable address is dependent on the PLC type
Update cycle
HIGH, MIDDLE, or LOW
(upper and lower cases are not distinguished)
Data type
INT (integer),
DINT (double-word integer),
UINT (unsigned integer),
UDINT (unsigned double-word integer),
HEX (hexadecimal),
DHEX (double-word hexadecimal),
REAL (floating-point data),
BOOL (logic),
BCD (binary coded decimal), or
DBCD (double-word BCD)
Default is INT (integer)
(upper and lower cases are not distinguished)
Setting example:
T
PLC1TAG00
RW005
HIGH
INT
T
PLC1TAG01
D1234
HIGH
INT
:
T
PLC1TAG32
X0002
MIDDLE
BOOL
T
PLC1TAG33
D4000
MIDDLE
INT
:
T
PLC1TAG64
D2500
LOW
INT
:
Up to 32 Tags for High update cycle
Up to 32 Tags for Middle update cycle
Up to 32 Tags for Low update cycle