Operation Manual
19
4. Configuration File
4.2.1 Connection setting
The connection setting specifies the connection name, type of connection (Ethernet or Serial),
Time-out setting, and Update cycles (High, Middle and Low).
The setting details and the column order are as follows.
Setting ID
C
Connection name
Any name (within 11 characters)
Type of connection
Ethernet or Serial
Time-out (in second)
Response time-out setting
Minimum 0.2 (0.1 s increments)
High update cycle
(in second)
High-speed update cycle setting
Minimum 0.2 (0.1 s increments)
Middle update cycle
(in second)
Middle-speed update cycle setting
Minimum 0.3 (0.1 s increments)
It must be larger than high-speed setting
Low update cycle
(in second)
Low-speed update cycle setting
Minimum 0.4 (0.1 s increments)
It must be larger than middle-speed setting
4.2.2 Serial setting
If the connection setting is serial, the serial setting is required.
The serial setting specifies the computer's communication port, baudrate, data bit length, parity,
and stop bit length.
The setting details and the column order are as follows.
Setting ID
CS
Communication port
COM1, COM2, COM3, or COM4
Baudrate
1200, 2400, 4800, 9600, or 19200 bps
Data bit length
8 (fixed)
Parity
ODD, EVEN, or NON
(upper and lower cases are not distinguished)
Stop bit length
1 or 2
Note) When the programmer port or TOSLINE-S20 is used, set the communication parameter
as follows.
•
Baudrate : 9600 bps
•
Data bit :
8 bits
•
Parity :
Odd (for Programmer port) or Even (for TOSLINE-S20) at default state
(Parity can be changed by user)
•
Stop bit :
1 bit