- 38 -
◆
Various display item operation examples
Example to change the display title
You can use UP or DOWN to change the display title.
Example) 0. StAt
→
UP
→
1. Set
Example to change the setting value of a detailed item
After changing the display title, you can touch ENTER to display the detailed item and then
display the setting value. You can use UP or DOWN to change the detailed item. Also, you can
return to the title display by touching BACK from the detailed item screen.
When entering water temperature is 20°C and leaving water temperature is 10°C
Example) 2. tH-1
→
ENTER
→
Et
→
20 (Display detailed item)
Et
→
20
→
UP
→
Lt
→
10 (Change the detailed item)
Et
→
20
→
BACK
→
2. tH-1 (Return to the title display)
Example to change the setting value of a detailed item (unit module operation)
After displaying the setting value of the detailed item, touch ENTER to make the setting value
flash. Change the setting value with UP or DOWN while it flashes and then confirm the setting
with ENTER. After changing the setting value, touch BACK to return to the detailed display
screen.
When changing the set water temperature (cooling) from 7°C to 6.8°C
Example)
SP-C
→
7.0
→
ENTER
→
"7.0"
→
DOWN
→
"6.8"
1.SEt
←
BACK
←
6.8
←
ENTER
(4) DN code table based on pump horsepower difference
* After delivery of the heat pump, check to ensure the pumps horsepower setting of the DN code
correlates to the heat pump's nameplate.
1. Use UP and DOWN to select "C.dnSt", and then ENTER to confirm.
2. After d-
○○○
appears, the set value appears. After "d-
○○○
" appears, the shown DN code number is indicated. The set value
is shown in "
●
".
3. Use UP and DOWN to change the DN code number. When a desired DN code number (d-0CF) is selected, the value for
each horsepower as listed in the table also appears. Check that the pump horsepower indicated on the installed pump
name plate is the same as the pump horsepower value displayed.
4. If they are different, change the displayed value, as follows:
●
Touch ENTER to confirm. The value flashes so that you can change it.
●
When the value is still flashing, use UP and DOWN to change the displayed value to the correct value for the pump
horsepower, and then touch ENTER to confirm.
5. Finally, use BACK to return to the default value such as "Cool".
DN code
Function
Pump HP
Setting value
1.5 kW (50 HP , 60 HP standard)
2
2.2 kW (70 HP standard)
3
3.7 kW
4
5.5 kW
5
7.5 kW
6
CF
Pump HP setting
C
d
n
S
●
●
●
●
Checking and setting DN code
t
d
-
○
○
○
●