- 32 -
03. Setup operation data storage screen
• Select "03. Setup operation data storage" from
. The
screen on the left appears.
• You can switch the save interval and save items with
and
.
• You can change the save interval item with
and
.
• You can change the number of data items to save with
and
.
• The factory default is to log "System data 1" at an interval of "1
min". Old log entries are overwritten after one month. It is also
possible to suppress the overwriting (Contact Toshiba Carrier
for details). Keep in mind that logging is disabled when the
storage area becomes full. The following table gives ballpark
figures for the maximum amount of data that can be stored.
Maximum amount of stored data
Number of connected
heat pumps
Save
interval
Save
period
Saved items
Approximate
guide
8
1 minute
24 hours System data 1
945 months
8
1 minute
24 hours System data 1 + UC data 1
140 months
8
1 minute
24 hours System data 1 + UC data 1 + System data 2
133 months
8
1 minute
24 hours System data 1 + UC data 1 + System data 2 + UC data 2
115 months
16
1 minute
24 hours System data 1
873 months
16
1 minute
24 hours System data 1 + UC data 1
70 months
16
1 minute
24 hours System data 1 + UC data 1 + System data 2
68 months
16
1 minute
24 hours System data 1 + UC data 1 + System data 2 + UC data 2
58 months
Always use "SD Formatter" to format the SD card.
(Refer to the SD Formatter instructions for details on how to use it.)
URL for download:
https://www.sdcard.org/jp/downloads/formatter_4/eula_windows/index.html