Branch Kit 1:3
<RAV-SM2244AT, SM2804AT series>
CAUTION
When planning a layout for Units A, B and C, comply with the following:
1. The lengths after branching (“a” and “b”, “b” and “c”, “a” and “c”) should be equal if
feasible. Install Units A, B and C so that the difference of the branching lengths becomes
less than 10 m if the lengths cannot be equal due to the branch pipe position.
2. Install Units A, B and C on the same level. If Units A, B and C cannot be installed on the
same level, the difference in level should be limited to 0.5 m or less.
Refrigerant
pipe
specifications
Pipe length
(one way)
Total length (L + a, L + b, L + c)
70 m
Branch pipe length (a, b, c)
20 m
Maximum difference between indoor units
(|a - b|, |b - c|, |c - a|)
10 m
Height
difference
Between indoor units (
Δ
h)
0.5 m
Between indoor
unit and outdoor
unit
When outdoor unit is higher (H)
30 m
When outdoor unit is lower (H)
30 m
Number of bent portions
10 or less
L
a
b
c
H
Indoor unit B
Indoor unit A
Indoor unit C
Branch pipe
Branch pipe
Main pipe
Branch pipe
Distributor