9
EN
Branch Kit 1:3
Distributor
Now the refrigerant pipe is installed using distributor supplied as accessory.
•
Bend and adjust the refrigerant piping so that the distributor and pipe after branching
become horizontal.
•
Fix the distributor onto a wall in a ceiling or onto a column.
•
Provide a straight pipe longer than 500 mm in length as the main piping of the branches.
How to install distributor
Restrictions in length of the straight area of the branch pipe (main pipe side)
Provide a straight area of 500 mm or more on the main pipe side of the branch pipe (for both
gas pipe and liquid pipe sides).
Air Purging
For the complete information, read the installation manual for outdoor units of air
conditioner.
Branch pipes are
horizontal and collective
pipes are vertical
Branch pipes and collective
pipes are horizontal
Branch pipe
Collective pipe
Branch pipes are
horizontal and collective
pipes are vertical
Branch pipes and collective
pipes are horizontal
Branch pipe
Collective pipe
<Gas pipe side>
<Liquid pipe side>
500 mm
or more
Be sure to install the pipes
horizontally after branching.
Tilt
NO GOOD
500 mm
or more