– 6
2
–
FILE NO. SVM-13047
Is connection of CN603 correct?
Is resistance value of TD sensor correct?
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
Is connection of CN601 correct?
Is resistance value of TE sensor correct?
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
Is connection of CN604 correct?
Is resistance value of TL sensor correct?
Correct connector.
Sensor error
→
Replace
Check outdoor P.C. board.
Defect
→
Replace
YES
NO
Check
code
[F04]
[F06]
[F07]
Outdoor
LED display
<Display 1> <Display 2>
<Display 1> <Display 2>
<Display 1> <Display 2>
<Display 1> <Display 2>
<Display 1> <Display 2>
<Display 1> <Display 2>
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Discharge temp. sensor (TD) error]
s
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is.
Heat exchanger temp. sensor (TE) error, Heat exchanger temp. sensor (TL) error,
Suction temp. sensor (TS) error, Miswiring of heat exchanger sensor (TE, TS)
Heat exchanger temp. sensor (TE) error]
[Heat exchanger temp. sensor (TL) error]
→
Refer to
[F07]
column.
[Suction temp. sensor (TS) error]
→
Refer to
[F12]
column.
[Miswiring of heat exchanger sensor (TE, TS)]
→
Refer to
[F15]
column.
[Heat exchanger temp. sensor (TL) error]
<In case of SP80>
SVM-12085_051-114.indd 63
SVM-12085_051-114.indd 63
12/06/12 11:15 AM
12/06/12 11:15 AM
Summary of Contents for RAV-SP564ATP-A
Page 17: ... 17 FILE NO SVM 13047 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SP56 ATP ...
Page 18: ... 18 FILE NO SVM 13047 2 2 RAV SP80 ATP ...
Page 23: ... 23 FILE NO SVM 13047 1 4 WIRING DIAGRAM 4 1 RAV SP56 ATP ...
Page 24: ... 24 FILE NO SVM 13047 4 2 RAV SP80 ATP ...
Page 100: ... 100 FILE NO SVM 13047 1 11 1 RAV SP564ATP A 11 EXPLODED VIEWS AND PARTS LIST ...
Page 104: ... 104 FILE NO SVM 13047 11 2 RAV SP804ATP A ...
Page 109: ......