– 14 –
FILE NO. SVM-13047-1
1. SPECIFICATIONS
1-1. Outdoor Unit
Model name
Outdoor unit
RAV-SP
564ATP
*
804ATP
*
Power supply
1 phase 220-240V 50Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Motor
(kW)
1.1
1.1
Pole
4
4
Refrigerant
charged
(kg)
1.4
2.1
Refrigerant control
Pulse motor valve
Inter
connecting
pipe
Standard length
(m)
7.5
7.5
Min. length
(m)
5
5
Max. total length
(m)
50
50
Additional refrigerant charge
under long piping connector
40g/m
(21m to 50m)
40g/m
(31m to 50m)
Height
difference
Outdoor lower
(m)
30
30
Outdoor higher
(m)
30
30
Outer
dimension
Height (mm)
550
890
Width (mm)
780
900
Depth (mm)
290
320
Appearance
Silky shade (Muncel 1Y8.5/0.5)
Total weight
(kg)
44
63
Heat exchanger
Finned tube
Fan unit
Fan
Propeller fan
Standard air -ow high
(m
3
/min.)
40
50
Motor (W)
43
63
Connecting
pipe
Gas side
(mm)
12.7
15.9
Liquid side
(mm)
6.4
9.5
Sound pressure level
Cooling/Heating (dB
·
A)
47/48
48/49
Sound power level
Cooling/Heating (dB
·
A)
63/64
64/65
Outside air temperature, Cooling
(°C)
43 to -15
Outside air temperature, Heating
(°C)
15 to -20
SVM-12085_001-050.indd 14
SVM-12085_001-050.indd 14
12/06/12 11:06 AM
12/06/12 11:06 AM
<Super Digital Inverter>
Summary of Contents for RAV-SP564ATP-A
Page 17: ... 17 FILE NO SVM 13047 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SP56 ATP ...
Page 18: ... 18 FILE NO SVM 13047 2 2 RAV SP80 ATP ...
Page 23: ... 23 FILE NO SVM 13047 1 4 WIRING DIAGRAM 4 1 RAV SP56 ATP ...
Page 24: ... 24 FILE NO SVM 13047 4 2 RAV SP80 ATP ...
Page 100: ... 100 FILE NO SVM 13047 1 11 1 RAV SP564ATP A 11 EXPLODED VIEWS AND PARTS LIST ...
Page 104: ... 104 FILE NO SVM 13047 11 2 RAV SP804ATP A ...
Page 109: ......