– 4
2
–
FILE NO. SVM-13047
10. Defrost control
<SP56 only>
1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to D
zone.
2) During defrosting operation, it finishes if TE sensor continued 12°C or continued 5°C
≤
TE < 12°C for
80 seconds. The defrost operation also finishes when it continued for 15 minutes even if TE sensor
temperature was 5°C or lower.
3) After defrost operation was reset, the compressor stopped for approx. 40 seconds and then the heating
operation starts.
∗
The minimum TE value and To value between 10 and 15 minutes after heating operation has started are
stored in memory as TE0 and To0, respectively.
0
10
15
29
35
91
[min.]
∗
TE [˚C]
–4
–6
–10
–25
A zone
A zone
B zone
B zone
C zone
C zone
Start of heating operation
D zone
D zone
A zone
B zone
C zone
D zone
o
T
l
a
m
r
o
n
b
a
n
I
o
T
l
a
m
r
o
n
n
I
When status (TE0 – TE) – (To0 – To)
≥
3°C
When status (TE0 – TE)
≥
3°C
s
d
n
o
c
e
s
0
2
r
o
f
d
e
u
n
i
t
n
o
c
s
d
n
o
c
e
s
0
2
r
o
f
d
e
u
n
i
t
n
o
c
When status (TE0 – TE) – (To0 – To)
≥
2.5°C
When status (TE0 – TE)
≥
2.5°C
s
d
n
o
c
e
s
0
2
r
o
f
d
e
u
n
i
t
n
o
c
s
d
n
o
c
e
s
0
2
r
o
f
d
e
u
n
i
t
n
o
c
When the status (TE
≤
–26°C) continued for 20 seconds
When the status (TE
≤
–10°C) continued for 20 seconds
SVM-12085_001-050.indd 43
SVM-12085_001-050.indd 43
12/06/12 11:06 AM
12/06/12 11:06 AM
Summary of Contents for RAV-SP564ATP-A
Page 17: ... 17 FILE NO SVM 13047 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SP56 ATP ...
Page 18: ... 18 FILE NO SVM 13047 2 2 RAV SP80 ATP ...
Page 23: ... 23 FILE NO SVM 13047 1 4 WIRING DIAGRAM 4 1 RAV SP56 ATP ...
Page 24: ... 24 FILE NO SVM 13047 4 2 RAV SP80 ATP ...
Page 100: ... 100 FILE NO SVM 13047 1 11 1 RAV SP564ATP A 11 EXPLODED VIEWS AND PARTS LIST ...
Page 104: ... 104 FILE NO SVM 13047 11 2 RAV SP804ATP A ...
Page 109: ......