background image

� 17 �

13

 Troubleshooting

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. Board of the outdoor unit in addition

to using the check codes displayed on the wired remote controller of the indoor unit.

Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote

controller of the indoor unit are described in the Installation Manual of the indoor unit.

 

LED displays and check codes

No.

Error

Display

D800 D801 D802 D803 D804 D805

1

Normal

2

Discharge temperature sensor (TD) error

3

Heat exchanger temperature sensor (TE) error

4

Heat exchanger temperature sensor (TL) error

5

Outside air temperature sensor (TO) error

6

Suction temperature sensor (TS) error

7

Heat sink temperature sensor (TH) error

8

Heat exchanger sensor (TE, TS) connection error

9

EEPROM error

10

Compressor breakdown

11

Compressor lock

12

Current detection circuit error

13

Case thermostat operation

14

Model data not set

15

Discharge temperature error

16

Power supply error

17

High pressure SW error

18

Heat sink overheating error

19

Gas leak detected

20

4-way valve reverse error

21

High pressure release operation

22

Fan system error

23

Drive device short-circuiting

24

Position detection circuit error

25

Compressor IPDU or other (not specifically identified)

 : ON,    : OFF,  

 : Rapid flashing (5 times/sec)

 
 

* The LEDs and switches are located at the top right

 

  of the P.C. Board of the outdoor unit as shown in the

 

  figure on the table below.

LED displays

D800

(Yellow)

D801

(Yellow)

D802

(Yellow)

D803

(Yellow)

D804

(Yellow)

D805

(Green)

33-EN

34-EN

14

   Appendix

[1] Existing piping

Work instructions

The existing R22 and R407C piping can be reused for

our digital inverter R410A product installations.

 

WARNING

Confirming the existence of scratches or

dents on the existing pipes and confirming the

reliability of the pipe strength are conventionally

referred to the local site.

If the specified conditions can be cleared, it is

possible to update existing R22 and R407C pipes

to those for R410A models.

Basic conditions needed to reuse

existing pipes

Check and observe the presence of three conditions

in the refrigerant piping works.

1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

Tight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should

not be reused as they are. Clean the existing pipes

or exchange them with new pipes.

1.  When a scratch or dent is heavy, be sure to use

  new pipes for the refrigerant piping works.

2.  When the existing pipe thickness is thinner than the  

  specified “Pipe diameter and thickness,” be sure to  

  use new pipes for the refrigerant piping works.

  • The operating pressure of R410A is high

    (1.6 times that of R22 and R407C). If there is a

    scratch or dent on the pipe or a thinner pipe is

    used, the pressure strength may be inadequate,

    which may cause the pipe to break in the worst

   case.

* Pipe diameter and thickness (in (mm))

Pipe outer diameter

1/4” (6.4)

3/8” (9.5) 1/2” (12.7)

Thickness R410A 0.03” (0.8) 0.03” (0.8) 0.03” (0.8)

3.  When the outdoor unit was left with the pipes

  disconnected, or the gas leaked from the pipes and

  the pipes were not repaired and refilled.

  • There is the possibility of rain water or air,

    including moisture, entering the pipe.

4.  When refrigerant cannot be recovered using a

  refrigerant recovery unit.

  • There is the possibility that a large quantity of

    dirty oil or moisture remains inside the pipes.

5.  When a commercially available dryer is attached to

  the existing pipes.

  • There is the possibility that copper green rust has

    been generated.

6.  When the existing air conditioner is removed after

  refrigerant has been recovered.

  Check if the oil is judged to be clearly different from

  normal oil.

  • The refrigerator oil is copper rust green in color:

    There is the possibility that moisture has mixed

    with the oil and rust has been generated inside

    the pipe.

  • There is discolored oil, a large quantity of

    residue, or a bad smell.

  • A large quantity of shiny metal dust or other wear

    residue can be seen in the refrigerant oil.

7.    When the air conditioner has a history of the

    compressor failing and being replaced.

  • When discolored oil, a large quantity of residue,

    shiny metal dust, or other wear residue or

    mixture of foreign matter is observed, trouble will

   occur.

8.  When temporary installation and removal of the air

  conditioner are repeated such as when leased etc.

9.  If the type of refrigerator oil of the existing air

  conditioner is other than the following oil (Mineral

  oil), Suniso, Freol-S, MS (Synthetic oil), alkyl

  benzene (HAB, Barrel-freeze), ester series, PVE

  only of ether series.

  • The winding-insulation of the compressor may

   deteriorate.

NOTE

  The above descriptions are results have been

  confirmed by our company and represent our

  views on our air conditioners, but do not guarantee

  the use of the existing pipes of air conditioners

  that have adopted R410A in other companies.

Curing of pipes

When removing and opening the indoor or outdoor

unit for a long time, cure the pipes as follows:

•  Otherwise rust may be generated when moisture or

  foreign matter due to condensation enters the pipes.

•  The rust cannot be removed by cleaning, and new

  pipes are necessary.

Placement

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

1131701101-00_S01_297x210_60p_S_p70_220426.indd   17

26/4/2565   11:41:11

Summary of Contents for RAV-SP122AT2P-UL

Page 1: ...al Outdoor Unit Model name Heat Pump Model RAV SP122AT2P UL RAV SP182AT2P UL 1131701101 For commercial use Pour usage commercial Para uso comercial English Installation Manual 1 1131701101 00_S01_297x210_60p_S_p70_220426 indd 1 26 4 2565 11 41 08 ...

Page 2: ... 14 13 Troubleshooting 17 14 Appendix 17 15 Specifications 18 1 EN 2 EN Original instruction Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer the Installation Manual attached to the indoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an...

Page 3: ... Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Manufacturer He or she has been trained to install repair maintain relocate and remove the air conditioners made by Manufacturer or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained an...

Page 4: ...equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the ...

Page 5: ...ty guards or by by passing any of the safety interlock switches Do not touch the intake or aluminium fins of the outdoor unit Doing so may result in injury Tighten the flare nut with a torque wrench in the specified manner Excessive tightening of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage Install the air conditioner securely in a lo...

Page 6: ...gerant pipe Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will cause air etc to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupturing injury etc WARNING After installation work make sure below before operation Connection pipes are connected properly and no leakag...

Page 7: ...unit and installation tools are different from those of the conventional refrigerant units Accordingly special tools are required for the new refrigerant R410A units For connecting pipes use new and clean piping materials with high pressure fittings made for R410A only so that water and or dust does not enter Required Tools Equipment and precautions for use Prepare the tools and equipment listed i...

Page 8: ...ves on the gas and liquid sides 2 Pressurize the pipe with nitrogen gas charged from the service port to the design pressure 4 15 MPa to conduct an leakage test 3 Check for gas leaks using a leak tester for the HFC refrigerant 4 After the leakage test is completed evacuate the nitrogen gas Evacuation To evacuate system use a vacuum pump Do not use refrigerant charged in the outdoor unit for evacua...

Page 9: ...ere the operating noise of the outdoor unit is transmitted When the outdoor unit is installed in an elevated position be sure to secure its feet A location in which drain water poses any problems When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building one of the following is recommended Install the unit so that its di...

Page 10: ...oundation for an outdoor unit with downward piping consider the piping work Absorb vibration with vibration proof rubber pads Fixing leg Correct Correct Foundation Foundation Foundation Bottom plate of outdoor unit Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit Incorrect Do not support the outdoor unit only with the fixing l...

Page 11: ...eck for gas leaks at connected points Tightening of flare connections 1 Align the centers of the flare connections and fully tighten the flare nuts with your fingers Valve at liquid side 2 Use two wrenches to loosen or tighten the flare nut on the gas service valve as shown in the figure Use only one wrench to loosen or tighten the flare not on the liquid service valve The final tightening with a ...

Page 12: ... Unit 500 microns Low side valve High side valve Vacuum pump Packed valve at gas side Charge port Valve core Setting pin Indoor Unit Service Valve High Side Refrigerant Low Side Charge hose Charge hose Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method...

Page 13: ...ntil and the gauge of manifold dropped into the range of 0 5 0 kgf cm2 8 Use the Hexagon wrench to turning the valve rod of Gas side fully close And turn off the Air Conditioner system immediately thereafter 9 Remove the gauge manifold from the service port of the packed valve 10 Securely tighten the valve rod cap to the both service valves CAUTION Should be check the compressor operating conditio...

Page 14: ...rconnections should be minimum 16 AWG Stripping length power cord and connecting wire Ground wire in mm Ground wire System interconnection wire Power supply wire How to wire 1 Remove the terminal cover by taking off the mounting screw 1 piece 2 Connect the power supply wires and system interconnection wires to the terminal block of the electrical control box 3 Tighten the screws of the terminal bl...

Page 15: ...due to the high frequency wave generated by the frequency converter inverter in the outdoor unit If you touch the charged outdoor unit without a grounding wire you may experience an electric shock 9 Finishing After the refrigerant pipe inter unit wires and drain pipe have been connected make sure they are supported and fixed in place for the entire length Keep the power wires and system interconne...

Page 16: ... the course of this operation hold down SW01 and SW02 simultaneously for at least 5 seconds to return to the initial status and then repeat the steps for recovering the refrigerant 29 EN 30 EN Refrigerant recovery When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit the recovery operation can be performed by operating the SW01 and SW02 switches on th...

Page 17: ...indicated when step 4 is taken D800 D801 D802 D803 D804 D805 ON OFF Slow flashing EN 31 EN 32 EN Existing piping The following settings are required when using a pipe Ø3 4 19 1 mm as the existing piping at the gas pipe side Steps taken to support existing piping 1 Set the circuit breaker to the ON position to turn on the power 2 Check that the LED displays are placed in their initial status If not...

Page 18: ...he specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works The operating pressure of R410A is high 1 6 times that of R22 and R407C If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness in mm Pipe outer diameter 1 4 6 4 3 8 9 5...

Page 19: ...e the enclosed refrigerant label adjacent to the charging and or recovering location 2 Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink Then place the included transparent protective sheet over the label to prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluorinated greenhouse gas is neve...

Page 20: ...s almost non existent If a conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its concentration does not reach the limit and in the event of an emergency measures can be made before injury can occur In a room where the concentration may exceed the limit create an opening with adjacent rooms or i...

Page 21: ...1131701101 1131701101 00_S01_297x210_60p_S_p70_220426 indd 59 26 4 2565 11 41 31 ...

Reviews: