– 19 –

12

Test run

„

Before test run

• Before turning on the power supply, carry out the 

following procedure.

1) By using 500 V-megger, check that resistance 

of 1 M

Ω

 or more exists between the terminal 

block 1 to 3 and the earth (grounding).
If resistance of less than 1 M

Ω

 is detected, do 

not run the unit.

2) Check the valve of the outdoor unit being 

opened fully.

• To protect the compressor at activation time, leave 

power-ON for 12 hours or more before operating.

„

Execute a test run

Operate the unit with the wired remote controller as 
usual.
For the procedure of the operation, refer to the 
attached Owner’s Manual.
A forced test run can be executed in the following 
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.

CAUTION

Do not use the forced test run for cases other than the 
test run because it applies an excessive load to the 
devices.

1

Push 

 button for 4 seconds or more. 

[TEST] is displayed on the display part and 
the selection of mode in the test mode is 
permitted.

2

Push  

button.

3

Select the operation mode with 

 

button, [

Cool] or [

Heat].

• Do not run the air conditioner in a mode other 

than [

Cool] or [

Heat].

• The temperature controlling function does not 

work during test run.

• The detection of error is performed as usual.

4

After the test run, push 

 button to 

stop a test run.
(Display part is same as procedure 

1

.)

5

Push 

 check button to cancel (release 

from) the test run mode.
([TEST] disappears on the display and the 
status returns to a normal.)

2, 4
3

1,5

„

When a test run is not 
performed properly

When a test run is not performed properly, refer to the 
error code and the part to be checked on 
“Troubleshooting”.

In case of wireless remote controller 

(Forced test operation is performed in a 

different way.)

REQUIREMENT

• For the operation procedure, be sure to follow the 

Owner’s Manual.

• Finish the forced cooling operation in a short time 

because it applies excessive strength to the air 
conditioner.

• A test operation of forced heating is unavailable. 

Perform a test operation by heating operation using 
the switches of the remote controller.
However heating operation may be not carried out 
according to the temperature conditions.

Check wiring / piping of indoor and outdoor units

1

When 

 button is pushed for 10 seconds or 

more, “Pi!” sound is heard and the operation 
changes to a forced cooling operation. After 
approx. 3 minutes, a cooling operation starts 
forcedly.
Check cool air starts blowing. If the 
operation does not start, check wiring again.

2

To stop a test operation, push 

 button 

once again (approx. 1 second).
The louver closes and the operation stops.

• Check transmission of remote controller

3

Push 

 button of the remote controller 

to check an operation can also start by the 
remote controller.

• “Cooling” operation by the remote controller 

may be unavailable according to the 
temperature conditions.
Check wiring / piping of the indoor and outdoor 
units in forced cooling operation.

37-EN

38-EN

+001111055801_01EN.book  Page 19  Monday, September 5, 2011  11:12 AM

Summary of Contents for RAV-SM566KRT-E

Page 1: ...xxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx AIR CONDITIONER SPLIT TYPE Indoor Unit Model name High Wall Type RAV SM566KRT E RAV SM806KRT E Installation Manual For commercial use 001111055801_01EN book Page 1 Monday September 5 2011 11 12 AM ...

Page 2: ...llation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an indivi...

Page 3: ...tection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not...

Page 4: ...t the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Refrigerant piping Install the refrigerant pipe securely during the ins...

Page 5: ...ompanied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the ...

Page 6: ...unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not b...

Page 7: ...cooled well Screen OK NO GOOD 5 Cutting a hole and mounting installation plate Cutting a hole In case of installing the refrigerant pipes from the rear 1 Decide the hole position for piping at 180 mm from the arrow mark Ö on the installation plate and drill a hole at a slight downward slant toward outdoor side Pipe hole dia 65 mm SM56 type Pipe hole dia 80 mm SM80 type NOTE When drilling a wall th...

Page 8: ...e drain cap by needle nose pliers and pull out How to fix the drains cap 1 Insert hexagonal wrench dia 4 mm in a centre head 2 Firmly insert drains cap CAUTION Firmly insert the drain hose and drain cap otherwise water may leak How to remove the drain hose 1 Remove the front panel 2 Remove the screws of drain hose 3 Pull out the drain hose How to fix the drain hose 1 Put the drain hose 2 Screw the...

Page 9: ... of the gas pipe locally procured leaving a 10 mm overlap with the shield of the shield pipe Liquid side Gas side System interconnection wire Indoor unit Auxiliary pipes Installation plate Wired remote controller wiring 1 2 Press unhook Hook Hook here Installation plate Push Push screw screw 8 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the...

Page 10: ...nventional tool used 6 4 9 5 0 to 0 5 1 0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Work using double spanner Outer dia of connecting pipe mm Tightening torque N m 6 4 14 to 18 1 4 to 1 8 kgf m 9 5 33 to 42 3 3 to 4 2 kgf m 12 7 50 to 62 5 0 to 6 2 kgf m 15 9 63 to 77 6 3 to 7 7 kgf m Open the valve fully Open the valve of the outdoor unit fully A h...

Page 11: ...emote controllers Up to 300 m 2 remote controllers including a wireless remote controller Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m A B L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller max 8 units Remote controller wiring Wiring between indoor unit and outdoor unit 1 Figure below shows t...

Page 12: ...y System interconnection wire 3 is not used 3 Connect the earth wire to the earth screw located on the underside of the electrical control box 4 Clamp the system interconnection wire with the cord clamp 5 Attach the terminal cover and the air intake grille to the indoor unit When using optional wired remote controller The system interconnection wire and the wired remote controller wire can be conn...

Page 13: ...e air conditioner before making settings CAUTION Set only the CODE No shown in the following table Do NOT set any other CODE No If a CODE No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push button and TEMP button simultaneously for 4 seconds or more After a while the display flashes as shown in the figure Confirm that the C...

Page 14: ...tting SET DATA Filter sign term 0000 None 0001 150 H factory default 0002 2500 H 0003 5000 H 0004 10000 H SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode Remote controller switch monitoring function This function is available to ...

Page 15: ...ire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setup of automatic address the remote controller operation is not accepted Required time up to the finish of automatic addressing is approx 5 minutes NOTE In some cases it is necessary to chan...

Page 16: ...k the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2 is repeated 7 After check of the changed contents push button setup is determined When button is pushed the display disappears and the status becomes the usual stop status when button is pushed the operation from the remote c...

Page 17: ...ptional wired remote controller Connect the central control wire to the terminals and on the terminal block in the same way as the optional wired remote controller For details refer to the installation manual of the applicable central control system SET DATA 8 C Operation setting 0000 None factory default 0001 8 C Operation setting Display changes according to the model No of indoor unit 3 4 3 4 2...

Page 18: ... C302 DB301 L301 SW01 T301 L41 L201 CN213 CN104 IC01 SW02 BZ01 CN101 CN102 MCC 1510 ON 1 2 ON 1 2 Factory default After setting SW01 OFF SW02 OFF SW01 ON SW02 OFF Centrally control the system by connecting to the TCC LINK central control system Setting central control addresses When air conditioners of the SDI DI series are connected to the TCC LINK central control system for central control using...

Page 19: ...change For 30 or more refrigeration systems when they are used together with the SMMS series the number of refrigeration systems of the SMMS series is included The line address change setting procedure for up to the 29th refrigeration system is the same as that described in step 1 on the previous page Since all line addresses are set to 1 except for group control by the automatic address setup fun...

Page 20: ...re 1 5 Push check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 When a test run is not performed properly When a test run is not performed properly refer to the error code and the part to be checked on Troubleshooting In case of wireless remote controller Forced test operation is performed in a different way REQUIREMENT ...

Page 21: ...nce can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance list Parts Inspection method Heat exchanger Acc...

Page 22: ...oor P C board No data is received from the remote controller or network adapter Auto reset E04 Indoor unit outdoor unit serial communication error Indoor System interconnection wires indoor P C board outdoor P C board Serial communication error between indoor unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same a...

Page 23: ...peration continued thermostat OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated was detected Entire stop Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked error description Airconditioner status Indication OperationTi...

Page 24: ...1111055801 001111055801_01EN book Page 65 Monday September 5 2011 11 12 AM ...

Reviews: