Piping and drain hose installation

„

Piping and drain hose forming

* Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of the 

equipment. (use polyethylene foam for insulating material.)

1. Remove the front panel

2. Die-cutting front panel slit

Cut out the slit on the leftward or right side of the front panel for the left or right connection and the slit on the bottom 
left or right side of the front panel for the bottom left or right connection with a pair of nippers.

3. Changing drain hose

For leftward connection, bottom-leftward connection and rear leftward connection's piping, it is necessary to 
change the drain hose and drain cap.
Without changing the drain hose position, the indoor unit will not fit to the wall.

How to remove the drain hose

The front panel must be removed for piping 
connections in the left, bottom left, and rear left 
directions.
• Open the air intake grille upward.
• Remove the four screws securing the front panel.
• Slightly open the lower part of the front panel, and 

then pull the upper part of the front panel toward you 
to remove it from the rear plate.

• The drain hose can be removed by removing the screw securing the drain hose and 

then pulling out the drain hose.

• When removing the drain hose, be careful of any sharp edges of steel plate. The 

edges can injuries.

• To install the drain hose, insert the drain hose firmly until the connection part 

contacts with heat insulator, and the secure it with original screw.

Piping 

preparation

Die-cutting 

front panel 

slit

Rear right

Rear left

Bottom left

Left

Bottom right

Right

Removing 

front panel

Changing 

drain hose

3

2

1

Air intake grille

Front panel

Heat insulator

Drain hose

How to remove the drains cap

Clip the drain cap by needle-nose pliers and pull out.

How to fix the drains cap

1

Insert hexagonal wrench (dia. 4 mm) in a 
centre head.

2

Firmly insert drains cap.

CAUTION

Firmly insert the drain hose and drain cap; otherwise, 
water may leak.

How to remove the drain hose

1

Remove the front panel.

2

Remove the screws of drain hose.

3

Pull out the drain hose.

How to fix the drain hose

1

Put the drain hose.

2

Screw the drain hose to the indoor unit.

3

Install the front panel.

In case of right or left piping

After scribing slits of the front panel with a knife or a 
marking-off pin, cut them with a pair of nippers or an 
equivalent tool.

In case of bottom right or bottom left piping

After scribing slits of the front panel with a knife or a 
marking-off pin, cut them with a pair of nippers or an 
equivalent tool.

Left-hand connection with piping

Bend the connecting pipe so that it is laid within 43 mm 
above the wall surface. If the connecting pipe is laid 
exceeding 43 mm above the wall surface, the indoor 
unit may unstably be set on the wall. When bending the 
connecting pipe, make sure to use a spring bender so 
as not to crush the pipe.

Bend the connection pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (figure)

NOTE

If the pipe is bent incorrectly, the indoor unit may 
unstably be set on the wall.
After passing the connecting pipe through the pipe hole, 
connect the connecting pipe to the auxiliary pipes and 
wrap the facing tape around them.

4 mm

No gap

Do not apply lubricating oil 

(refrigerant machine oil) 

when inserting the drain cap.

Application causes 

deterioration and drain 

leakage from the plug.

Insert a hexagon 

wrench (4 mm)

Slit

Slit

570 mm 

Outward 

form of 

indoor unit

(to the fore front of flare)

R 30 mm(use polish polyethylene core 

or the like for bending pipe.)

Gas 

side

Liquid side

Use the handle of screwdriver, etc.

420 mm 

43 mm

80

 °

13-EN

14-EN

+001111055801_01EN.book  Page 7  Monday, September 5, 2011  11:12 AM

Summary of Contents for RAV-SM566KRT-E

Page 1: ...xxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx xxxxxxxxxxxxxxxxxxxxxxxx xx Xxxxxxx AIR CONDITIONER SPLIT TYPE Indoor Unit Model name High Wall Type RAV SM566KRT E RAV SM806KRT E Installation Manual For commercial use 001111055801_01EN book Page 1 Monday September 5 2011 11 12 AM ...

Page 2: ...llation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an indivi...

Page 3: ...tection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not...

Page 4: ...t the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Refrigerant piping Install the refrigerant pipe securely during the ins...

Page 5: ...ompanied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the ...

Page 6: ...unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller may not b...

Page 7: ...cooled well Screen OK NO GOOD 5 Cutting a hole and mounting installation plate Cutting a hole In case of installing the refrigerant pipes from the rear 1 Decide the hole position for piping at 180 mm from the arrow mark Ö on the installation plate and drill a hole at a slight downward slant toward outdoor side Pipe hole dia 65 mm SM56 type Pipe hole dia 80 mm SM80 type NOTE When drilling a wall th...

Page 8: ...e drain cap by needle nose pliers and pull out How to fix the drains cap 1 Insert hexagonal wrench dia 4 mm in a centre head 2 Firmly insert drains cap CAUTION Firmly insert the drain hose and drain cap otherwise water may leak How to remove the drain hose 1 Remove the front panel 2 Remove the screws of drain hose 3 Pull out the drain hose How to fix the drain hose 1 Put the drain hose 2 Screw the...

Page 9: ... of the gas pipe locally procured leaving a 10 mm overlap with the shield of the shield pipe Liquid side Gas side System interconnection wire Indoor unit Auxiliary pipes Installation plate Wired remote controller wiring 1 2 Press unhook Hook Hook here Installation plate Push Push screw screw 8 Drainage 1 Run the drain hose sloped downwards NOTE Hole should be made at a slight downward slant on the...

Page 10: ...nventional tool used 6 4 9 5 0 to 0 5 1 0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Work using double spanner Outer dia of connecting pipe mm Tightening torque N m 6 4 14 to 18 1 4 to 1 8 kgf m 9 5 33 to 42 3 3 to 4 2 kgf m 12 7 50 to 62 5 0 to 6 2 kgf m 15 9 63 to 77 6 3 to 7 7 kgf m Open the valve fully Open the valve of the outdoor unit fully A h...

Page 11: ...emote controllers Up to 300 m 2 remote controllers including a wireless remote controller Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m A B L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller max 8 units Remote controller wiring Wiring between indoor unit and outdoor unit 1 Figure below shows t...

Page 12: ...y System interconnection wire 3 is not used 3 Connect the earth wire to the earth screw located on the underside of the electrical control box 4 Clamp the system interconnection wire with the cord clamp 5 Attach the terminal cover and the air intake grille to the indoor unit When using optional wired remote controller The system interconnection wire and the wired remote controller wire can be conn...

Page 13: ...e air conditioner before making settings CAUTION Set only the CODE No shown in the following table Do NOT set any other CODE No If a CODE No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push button and TEMP button simultaneously for 4 seconds or more After a while the display flashes as shown in the figure Confirm that the C...

Page 14: ...tting SET DATA Filter sign term 0000 None 0001 150 H factory default 0002 2500 H 0003 5000 H 0004 10000 H SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode Remote controller switch monitoring function This function is available to ...

Page 15: ...ire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setup of automatic address the remote controller operation is not accepted Required time up to the finish of automatic addressing is approx 5 minutes NOTE In some cases it is necessary to chan...

Page 16: ...k the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2 is repeated 7 After check of the changed contents push button setup is determined When button is pushed the display disappears and the status becomes the usual stop status when button is pushed the operation from the remote c...

Page 17: ...ptional wired remote controller Connect the central control wire to the terminals and on the terminal block in the same way as the optional wired remote controller For details refer to the installation manual of the applicable central control system SET DATA 8 C Operation setting 0000 None factory default 0001 8 C Operation setting Display changes according to the model No of indoor unit 3 4 3 4 2...

Page 18: ... C302 DB301 L301 SW01 T301 L41 L201 CN213 CN104 IC01 SW02 BZ01 CN101 CN102 MCC 1510 ON 1 2 ON 1 2 Factory default After setting SW01 OFF SW02 OFF SW01 ON SW02 OFF Centrally control the system by connecting to the TCC LINK central control system Setting central control addresses When air conditioners of the SDI DI series are connected to the TCC LINK central control system for central control using...

Page 19: ...change For 30 or more refrigeration systems when they are used together with the SMMS series the number of refrigeration systems of the SMMS series is included The line address change setting procedure for up to the 29th refrigeration system is the same as that described in step 1 on the previous page Since all line addresses are set to 1 except for group control by the automatic address setup fun...

Page 20: ...re 1 5 Push check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 When a test run is not performed properly When a test run is not performed properly refer to the error code and the part to be checked on Troubleshooting In case of wireless remote controller Forced test operation is performed in a different way REQUIREMENT ...

Page 21: ...nce can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance list Parts Inspection method Heat exchanger Acc...

Page 22: ...oor P C board No data is received from the remote controller or network adapter Auto reset E04 Indoor unit outdoor unit serial communication error Indoor System interconnection wires indoor P C board outdoor P C board Serial communication error between indoor unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same a...

Page 23: ...peration continued thermostat OFF P01 ALT Indoor unit fan error Indoor Indoor fan motor indoor P C board Indoor AC fan error fan motor thermal relay activated was detected Entire stop Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked error description Airconditioner status Indication OperationTi...

Page 24: ...1111055801 001111055801_01EN book Page 65 Monday September 5 2011 11 12 AM ...

Reviews: