– 71 –
ON-SITE SETTING AND OTHERS (Continued)
1.6 Monitoring Function of Remote Controller Switch
n
Calling indication of sensor temperature
<Description>
Calls the service monitor mode from the remote controller to
monitor sensor temperatures of the remote controller, indoor units,
and outdoor unit.
<Procedure>
1
Push
SET
and
CL
on the remote controller simultaneously for
4 seconds or more to call the service monitor mode.
“Service monitor” lights up and the header indoor unit number is
displayed first, and then temperature of code “
00
” is displayed.
2
Choose a sensor number (code) you want to monitor with
TEMP.
buttons.
The following table lists sensor numbers.
∗
1 Header indoor unit only under group control
3
Choose an indoor unit you want to monitor with
UNIT LOUVER
button to monitor sensor temperatures
of indoor units and outdoor unit in the same control group.
4
Push
TEST
to return to the normal indication.
Indoor unit data
Code
00
01
02
03
04
05
Data
Room temp. under control *1
Room temp. (Remote controller)
Indoor unit intake temp.
Indoor unit coil temp. TCJ
Indoor unit coil temp. TC
Indoor unit coil temp. TC1
Outdoor unit data
Code
60
61
62
63
64
65
Data
Heat exchange temp. TE
Outside air temp. TO
Discharge temp. TD
Intake temp. TS
—
Heatsink temp. THS
Operation procedure
1
→
2
→
3
→
4
Returns to normal indication
ON / OFF
SET
TEST
FILTER
RESET
CL
VE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
MODE
AN
SETTING
2 4
1
3