Wire connection

REQUIREMENT

• Connect the wires matching the terminal numbers. Incorrect connection causes.
• Pass the wires through the bushing of wiring connection port of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang down the electrical control box at servicing, or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)

• Before remove the electric parts cover, remove the cover plate and air filter.
• Remove the cover of the electrical control box by taking off the mounting screws (2 positions) and pushing the hooking 

section. (The cover of the electrical control box remains hanged to the hinge.)

• Tighten the screws of the terminal block, and fix the wires with cord attached to the electrical control box.

(Do not apply tension to the connecting section of the terminal block.)

• Set a loop for the connecting wire of the storing part of the indoor unit electric parts; otherwise the electrical control box cannot 

be drawn out in service time.

• Mount the cover of the electrical control box without pinching wires.

1 2 3

A B

Side D (Space: 8.5mm)

Side C (Space: 4mm)

Select side C or D for the power cable 
clamping position referring to the following 
table according to the cable type and 
diameter.
* Cable clamp can be attached on either 

right or left side.

When twin system are connected, clamp two 
cables with one cable clamp.

Wire 
type

Specification

Cable clamping 

position

Cabtyre 
cable

4-core stranded 
wire 2.5mm²

Side D

Cabtyre 
cable

4-core stranded 
wire 1.5mm²

Side C

Power supply 
terminal block

Remote controller 
terminal block

Cord clamp

Air filter

Electrical control

 box

Electrical control

 box cover

Screw
(2 positions)

Cover plate

Earth

Wiring

1

Remove a screw and then remove cover of the 
electrical control box.

2

Strip wire ends (10 mm).

3

Match wire colours with terminal numbers on indoor 
and outdoor units’ terminal blocks and firmly screw 
wires to the corresponding terminals.

4

Connect the ground wires to the corresponding 
terminals.

5

Fix the wire with cord clamp.

6

Fix cover of the parts box and the terminal block 
surely with the fixing screws.

Single system

Synchronous twin system

* For details of wiring/installation of the remote controller, 

refer to the Installation Manual enclosed to in the remote 
controller.

Remote Controller Wiring

• Strip off approx. 9 mm the wire to be connected.
• Non polarity, 2 core wire is used for wiring of the remote 

controller. (0.5 mm² to 2.0 mm² wires)

Wiring diagram

Make a loop on the wire for margin of the length so that 
the electrical control box can be taken out during 
servicing.

L
1

3

10

50

10

70

N

2

Connecting wire

Earth wire

A

B

1

1

L

N

2

2

3

3

Indoor side

System 
interconnecting 
wires

Remote controller

Remote controller 
wiring

Outdoor side

220-240V~

A

B

1

2

3

A

B

1

1

L

N

2

2

3

3

Indoor side

System 
interconnecting 
wires

Remote controller

Remote controller 
wiring

Outdoor side

Remote controller 
inter-unit wiring

Indoor power 
inter-unit wiring

Indoor 
side

220-240V~

A
B

A
B

Terminal block

Remote 
controller 
unit

Terminal block for 
remote controller 
wiring of indoor unit

Remote controller wire 
(Locally procured)

75-EN

76-EN

+00EH99885801-1_01EN.book  Page 38  Wednesday, October 8, 2014  12:02 PM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for RAV-SM304SDT-E

Page 1: ...uct Type RAV SM304SDT E RAV SM404SDT E RAV SM454SDT E RAV SM564SDT E English Installation Manual For commercial use For commercial use 00EH99885801 1_01EN book Page 1 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 2: ...t destruction of the ozone layer Contents 1 Precautions for safety 3 1 Précautions relatives à la sécurité 6 1 Sicherheitshinweise 9 1 Precauzioni per la sicurezza 12 1 Precauciones de seguridad 15 1 Precauções de segurança 18 1 Voorzorgen voor de veiligheid 21 1 Προφυλάξεις ασφαλείας 24 1 Правила техники безопасности 27 2 Accessory parts 29 3 Selection of installation place 29 4 Installation 31 5...

Page 3: ...edge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations b...

Page 4: ...ay fall off of the outdoor unit and result in injury When work is performed at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work Before cleaning the filter or other parts of the outdoor unit set the circuit breaker to OFF without fail and place a Work ...

Page 5: ...ch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power will not be turned on by marking out of service near the circuit breaker for instance until qualified service person arrives Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in elect...

Page 6: ...e d entretien qualifiée est une personne qui installe répare entretient déplace et enlève les climatiseurs fabriqués par Toshiba Carrier Corporation Il ou elle a été formé pour installer réparer entretenir déplacer et enlever les climatiseurs fabriqués par Toshiba Carrier Corporation ou alternativement il ou elle a reçu des consignes pour de telles opérations par une ou des personnes qui ont été f...

Page 7: ...t be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat exchanger and resin part turbo fan in the indoor unit may reduce the performance generate mist or dew drop or deform or damage resin parts Places where iron or other metal dust is present If iron or other metal dust adheres to...

Page 8: ...and service work Reference Dewing test conditions Indoor side 27 C dry bulb temperature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours 210 210 210 100 or more Floor surface Air discharge 250 or more 2500 or more 235 or more 5 or more Under air intake Back air intake 5 or more 5 or more Ceiling 50 or more 235 or more 235 or more 300 or more Floor surface 2500 or more Cei...

Page 9: ...man injury Perform a specified installation work to guard against strong wind or earthquake An incomplete installation can cause accidents by the units falling and dropping REQUIREMENT Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article on the indoor unit Even units are packaged Carry in the indoor unit as it is packaged if pos...

Page 10: ...ng work and insulating process are locally procured Flexible hose Insert the soft socket of the attached flexible hose into the connecting port of the drain pipe until it strikes against the end Align the attached hose band to the end of the pipe connecting port and then tighten it surely REQUIREMENT Be sure to fix the soft socket with the attached hose band and set the tightening position at uppe...

Page 11: ...in pipes CAUTION Pour water slowly If it is poured urgently water is spread inside of the indoor unit resulted in a trouble If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks and If doing so the drain pump motor operates Test water drain while c...

Page 12: ...tom surface CAUTION Take out this cover plate Connecting method of the duct CAUTION Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop Aluminum tape Locally procured Heat insulator with sticking material 100mm width Locally procured Aluminum tape Locally procured Duct Insulation material Locally procured Heat insulator with sticking m...

Page 13: ... 50Pa Lower limit of external static pressure 35Pa High 50Pa High 20Pa High 10Pa Standard filter pressure loss Standard air volume 690 m h Lower limit of external static pressure 20Pa 400 0 10 20 30 40 50 60 500 600 700 900 800 External static pressure Pa Air volume m h Upper limit of external static pressure 50Pa Upper limit of external static pressure 35Pa Upper limit of external static pressure...

Page 14: ...re pipe connections REQUIREMENT Tightening with an excessive torque may crack the nut depending on installation conditions Tighten the nut within the specified tightening torque Piping with outdoor unit Shape of valve differs according to the outdoor unit For details of installation refer to the Installation Manual of the outdoor unit Air purge Using a vacuum pump perform vacuuming from the charge...

Page 15: ...cause an electric shock or a fire CAUTION This indoor unit has no power cord If incorrect incomplete wiring is carried out it will cause an electrical fire or smoke Be sure to install an earth leakage breaker that is not tripped by shock waves If an earth leakage breaker is not installed an electric shock may be caused Be sure to use the cord clamps attached to the product Do not damage or scratch...

Page 16: ... C Power supply terminal block Remote controller terminal block Cord clamp Air filter Electrical control box Electrical control box cover Screw 2 positions Cover plate Earth Wiring 1 Remove a screw and then remove cover of the electrical control box 2 Strip wire ends 10 mm 3 Match wire colours with terminal numbers on indoor and outdoor units terminal blocks and firmly screw wires to the correspon...

Page 17: ...he display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from 2 To change other settings of the selected indoor unit repeat from 3 Use button to clear the settings To make settings after button was pushed repeat from 2 6 When settings have been completed push button to determine the settings When button is pushed SETTING flashes and then the d...

Page 18: ...e 0001 150H 0002 2500H factory default 0003 5000H 0004 10000H Setup data Detection temp shift value 0000 No shift 0001 1 C 0002 2 C factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Unit No 1 1 Unit No 1 2 Unit No 1 3 Unit No 1 4 Setting of power level in power saving mode Remote controller switch monitoring function This function is available to call the service monitor mode from the remote con...

Page 19: ...oller operation is not accepted Required time up to the finish of automatic addressing is approx 5 minutes NOTE In some cases it is necessary to change the address manually after setup of the automatic address according to the system configuration of the group control The above mentioned system configuration is a case when complex systems in which systems of the multiple twin unit is controlled as...

Page 20: ...e setup has finished push to select the indoor unit No before change of setup specify CODE No 12 13 14 in order with temp setup buttons and then check the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2 is repeated Procedure 7 After check of the changed contents push button Setu...

Page 21: ...n setting 0000 None Factory Shipping 0001 8 C Operation setting Display changes according to the model No of indoor unit 10Test run Before test run Before turning on the power supply carry out the following procedure To protect the compressor at activation time leave power ON for 12 hours or more before operating How to execute a test run Using the remote controller operate the unit as usual For t...

Page 22: ...on A 1 2 3 B 1 2 3 A 1 2 3 B A 1 2 3 B 1 2 3 A 1 2 3 B Incorrect connection Indoor unit Outdoor unit Remote controller Correct connection Indoor unit Outdoor unit Remote controller Disconnect the connection between indoor units Set the address again 1 Push and TIME buttons simultaneously for at least 4 seconds 2 flashes on the display as shown in the following figure 3 Push button changes from fla...

Page 23: ... and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried ou...

Page 24: ...E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E1...

Page 25: ...ror was detected in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power cable may be connected incorrectly Check open phase and voltages of the power supply Entire stop ...

Page 26: ... 48 MEMO 00EH99885801 1_01EN book Page 48 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 27: ... 49 MEMO 00EH99885801 1_01EN book Page 49 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 28: ... 50 MEMO 00EH99885801 1_01EN book Page 50 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 29: ...EH99885801 1 00EH99885801 1_01EN book Page 51 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Reviews: