Toshiba RAV-SM304SDT-E Installation Manual Download Page 14

– 36 –

7

Refrigerant piping

Refrigerant piping

1

If the outdoor units are to be mounted on a wall, 
make sure that the supporting platform is 
sufficiently strong. The platform should be 
designed and manufactured to maintain its strength 
over a long period of time, and sufficient 
consideration should be given to ensuring that the 
outdoor unit will not fall.

2

Use copper pipe with 0.8 mm or more thickness. 

3

Flare nut and flare works are also different from 
those of the conventional refrigerant.
Take out the flare nut attached to the main unit of 
the air conditioner, and use it.

REQUIREMENT

When the refrigerant pipe is long, provide support brackets 
at intervals of 2.5 to 3m to clamp the refrigerant pipe. 
Otherwise, abnormal sound may be generated.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Remove dust and moisture from the inside of the 

connecting pipes.

2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using VACUUM 

PUMP.

4. Check the gas leakage. (Connected points)

Pipe size

Permissible piping length and 
height difference

They vary according to the outdoor unit.
For details, refer to the Installation Manual attached to the 
outdoor unit.

Flaring

Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

Flaring dia. meter size : A (Unit : mm)

RAV-SM

Pipe size(mm)

Liquid side

Gas side

SM30

Ø6.4

Ø9.5

SM40, 45, 56

Ø6.4

Ø12.7

• Cut the pipe with a pipe cutter.

Remove burrs completely. 
Remaining burrs may cause gas leakage.

• Insert a flare nut into the pipe, 

and flare the pipe.
As the flaring sizes of R410A 
differ from those of refrigerant 
R22, the flare tools newly 
manufactured for R410A are 
recommended.
However, the conventional 
tools can be used by adjusting 
projection margin of the 
copper pipe.

Outer dia. of 

copper pipe

R410A tool used

Conventional 

tool used

R410A

R410A

6.4 , 9.5

0 to 0.5

1.5 to 2.0

12.7

Outer diam. of copper pipe

A

R410A

6.4

9.1

9.5

13.2

12.7

16.6

* In case of flaring for R410A with the 

conventional flare tool, pull it out approx.
0.5 mm more than that for R22 to adjust to 
the specified flare size.
The copper pipe gauge is useful for 
adjusting projection margin size.

B

+0
–0.4

A

Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may 
crack depending on the conditions.

Tightening torque of flare pipe connections

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

Shape of valve differs according to the outdoor unit.
For details of installation, refer to the Installation Manual of 
the outdoor unit.

Air purge

Using a vacuum pump, perform vacuuming from the charge 
port of valve of the outdoor unit.
For details, follow to the Installation Manual attached to the 
outdoor unit.
• Never use the refrigerant sealed in the outdoor unit for air 

purge.

REQUIREMENT

For the tools such as charge hose, etc., use those 
manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” 
referring to the attached Installation Manual of outdoor unit.
Be sure to use a scale to charge the refrigerant of specified 
amount.

REQUIREMENT

• Charging an excessive or too little amount of refrigerant 

causes of the compressor.
Be sure to charge the refrigerant of specified amount.

• A personnel who charged the refrigerant should write 

down the pipe length and the added refrigerant amount in 
the nameplate attached to the service panel of the 
outdoor unit. It is necessary to troubleshoot the 
compressor and refrigeration cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm-hexagonal 
wrench is required for opening the valve.
For details, refer to the Installation Manual attached to the 
outdoor unit.

(Unit : N•m)

Outer dia. of copper pipe

Tightening torque

6.4 mm (dia.)

14 to 18 (1.4 to 1.8 kgf•m)

9.5 mm (dia.)

34 to 42 (3.4 to 4.2 kgf•m)

12.7 mm (dia.)

49 to 61 (4.9 to 6.1 kgf•m)

Pressure of R410A is higher 
than that of R22.
(Approx. 1.6 times) 
Therefore, using a torque 
wrench, tighten the flare pipe 
connecting sections which 
connect the indoor and 
outdoor units of the specified 
tightening torque.
Incorrect connections may 
cause not only a gas leak, 
but also of the refrigeration 
cycle.
Align the centres of the 
connecting pipes and tighten 
the flare nut as far as 
possible with your fingers. 
Then tighten the nut with a 
spanner and torque wrench 
as shown in the figure.

Flare at 
indoor 
unit side

Flare at 
outdoor 
unit side

Externally 
threaded side

Half union

Flare nut

Internally 
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

71-EN

72-EN

+00EH99885801-1_01EN.book  Page 36  Wednesday, October 8, 2014  12:02 PM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for RAV-SM304SDT-E

Page 1: ...uct Type RAV SM304SDT E RAV SM404SDT E RAV SM454SDT E RAV SM564SDT E English Installation Manual For commercial use For commercial use 00EH99885801 1_01EN book Page 1 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 2: ...t destruction of the ozone layer Contents 1 Precautions for safety 3 1 Précautions relatives à la sécurité 6 1 Sicherheitshinweise 9 1 Precauzioni per la sicurezza 12 1 Precauciones de seguridad 15 1 Precauções de segurança 18 1 Voorzorgen voor de veiligheid 21 1 Προφυλάξεις ασφαλείας 24 1 Правила техники безопасности 27 2 Accessory parts 29 3 Selection of installation place 29 4 Installation 31 5...

Page 3: ...edge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations b...

Page 4: ...ay fall off of the outdoor unit and result in injury When work is performed at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work Before cleaning the filter or other parts of the outdoor unit set the circuit breaker to OFF without fail and place a Work ...

Page 5: ...ch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power will not be turned on by marking out of service near the circuit breaker for instance until qualified service person arrives Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in elect...

Page 6: ...e d entretien qualifiée est une personne qui installe répare entretient déplace et enlève les climatiseurs fabriqués par Toshiba Carrier Corporation Il ou elle a été formé pour installer réparer entretenir déplacer et enlever les climatiseurs fabriqués par Toshiba Carrier Corporation ou alternativement il ou elle a reçu des consignes pour de telles opérations par une ou des personnes qui ont été f...

Page 7: ...t be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat exchanger and resin part turbo fan in the indoor unit may reduce the performance generate mist or dew drop or deform or damage resin parts Places where iron or other metal dust is present If iron or other metal dust adheres to...

Page 8: ...and service work Reference Dewing test conditions Indoor side 27 C dry bulb temperature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours 210 210 210 100 or more Floor surface Air discharge 250 or more 2500 or more 235 or more 5 or more Under air intake Back air intake 5 or more 5 or more Ceiling 50 or more 235 or more 235 or more 300 or more Floor surface 2500 or more Cei...

Page 9: ...man injury Perform a specified installation work to guard against strong wind or earthquake An incomplete installation can cause accidents by the units falling and dropping REQUIREMENT Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article on the indoor unit Even units are packaged Carry in the indoor unit as it is packaged if pos...

Page 10: ...ng work and insulating process are locally procured Flexible hose Insert the soft socket of the attached flexible hose into the connecting port of the drain pipe until it strikes against the end Align the attached hose band to the end of the pipe connecting port and then tighten it surely REQUIREMENT Be sure to fix the soft socket with the attached hose band and set the tightening position at uppe...

Page 11: ...in pipes CAUTION Pour water slowly If it is poured urgently water is spread inside of the indoor unit resulted in a trouble If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks and If doing so the drain pump motor operates Test water drain while c...

Page 12: ...tom surface CAUTION Take out this cover plate Connecting method of the duct CAUTION Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop Aluminum tape Locally procured Heat insulator with sticking material 100mm width Locally procured Aluminum tape Locally procured Duct Insulation material Locally procured Heat insulator with sticking m...

Page 13: ... 50Pa Lower limit of external static pressure 35Pa High 50Pa High 20Pa High 10Pa Standard filter pressure loss Standard air volume 690 m h Lower limit of external static pressure 20Pa 400 0 10 20 30 40 50 60 500 600 700 900 800 External static pressure Pa Air volume m h Upper limit of external static pressure 50Pa Upper limit of external static pressure 35Pa Upper limit of external static pressure...

Page 14: ...re pipe connections REQUIREMENT Tightening with an excessive torque may crack the nut depending on installation conditions Tighten the nut within the specified tightening torque Piping with outdoor unit Shape of valve differs according to the outdoor unit For details of installation refer to the Installation Manual of the outdoor unit Air purge Using a vacuum pump perform vacuuming from the charge...

Page 15: ...cause an electric shock or a fire CAUTION This indoor unit has no power cord If incorrect incomplete wiring is carried out it will cause an electrical fire or smoke Be sure to install an earth leakage breaker that is not tripped by shock waves If an earth leakage breaker is not installed an electric shock may be caused Be sure to use the cord clamps attached to the product Do not damage or scratch...

Page 16: ... C Power supply terminal block Remote controller terminal block Cord clamp Air filter Electrical control box Electrical control box cover Screw 2 positions Cover plate Earth Wiring 1 Remove a screw and then remove cover of the electrical control box 2 Strip wire ends 10 mm 3 Match wire colours with terminal numbers on indoor and outdoor units terminal blocks and firmly screw wires to the correspon...

Page 17: ...he display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from 2 To change other settings of the selected indoor unit repeat from 3 Use button to clear the settings To make settings after button was pushed repeat from 2 6 When settings have been completed push button to determine the settings When button is pushed SETTING flashes and then the d...

Page 18: ...e 0001 150H 0002 2500H factory default 0003 5000H 0004 10000H Setup data Detection temp shift value 0000 No shift 0001 1 C 0002 2 C factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Unit No 1 1 Unit No 1 2 Unit No 1 3 Unit No 1 4 Setting of power level in power saving mode Remote controller switch monitoring function This function is available to call the service monitor mode from the remote con...

Page 19: ...oller operation is not accepted Required time up to the finish of automatic addressing is approx 5 minutes NOTE In some cases it is necessary to change the address manually after setup of the automatic address according to the system configuration of the group control The above mentioned system configuration is a case when complex systems in which systems of the multiple twin unit is controlled as...

Page 20: ...e setup has finished push to select the indoor unit No before change of setup specify CODE No 12 13 14 in order with temp setup buttons and then check the changed contents Address change check Before change 3 3 1 After change 2 2 2 Pushing button clears the contents of which setup was changed In this case procedure from 2 is repeated Procedure 7 After check of the changed contents push button Setu...

Page 21: ...n setting 0000 None Factory Shipping 0001 8 C Operation setting Display changes according to the model No of indoor unit 10Test run Before test run Before turning on the power supply carry out the following procedure To protect the compressor at activation time leave power ON for 12 hours or more before operating How to execute a test run Using the remote controller operate the unit as usual For t...

Page 22: ...on A 1 2 3 B 1 2 3 A 1 2 3 B A 1 2 3 B 1 2 3 A 1 2 3 B Incorrect connection Indoor unit Outdoor unit Remote controller Correct connection Indoor unit Outdoor unit Remote controller Disconnect the connection between indoor units Set the address again 1 Push and TIME buttons simultaneously for at least 4 seconds 2 flashes on the display as shown in the following figure 3 Push button changes from fla...

Page 23: ... and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried ou...

Page 24: ...E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E1...

Page 25: ...ror was detected in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power cable may be connected incorrectly Check open phase and voltages of the power supply Entire stop ...

Page 26: ... 48 MEMO 00EH99885801 1_01EN book Page 48 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 27: ... 49 MEMO 00EH99885801 1_01EN book Page 49 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 28: ... 50 MEMO 00EH99885801 1_01EN book Page 50 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 29: ...EH99885801 1 00EH99885801 1_01EN book Page 51 Wednesday October 8 2014 12 02 PM AMP Air Conditioning www ampair co uk sales ampair co uk ...

Reviews: