Applicable controls
REQUIREMENT
• When you use this air conditioner for the first time, it takes
approx. 5 minutes until the remote controller becomes
available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the settings.
Basic procedure for changing
settings
Change the settings while the air conditioner is not working.
(Be sure to stop the air conditioner before making settings.)
1
Push
button and temp. setup
button
simultaneously for at least 4 seconds or more.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push
button to erase
the display content, and repeat the procedure from
the beginning.
(No operation of the remote controller is accepted for
a while after
button is pushed.)
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs. You can confirm
the indoor unit for which you want to change
settings.
3
Using temp. setup
/
buttons, specify
CODE No. [
].
4
Using timer time
/
buttons, select
SET DATA [
].
* The settings cannot be changed using the wireless
remote controller, sub remote controller, or remote-
controllerless system (for central remote controller
only). Therefore, install the wired remote controller to
change the settings.
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 5 minutes
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 1 minutes
1
6
1
3
2
5
4
(* Display content varies with
the indoor unit model.)
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat from
2
.
• To change other settings of the selected indoor unit,
repeat from
3
.
Use
button to clear the settings.
To make settings after
button was pushed, repeat
from
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
External static pressure
settings
Be sure to set up a tap change based upon the resistance
(external static pressure) of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the item code in
3
.
• For the setup data of
4
, select a setup data of the external
static pressure to be set up from the following table.
<Change on wired remote controller>
◆
When wireless remote controller
is used
Change the external static pressure setting with the DIP
switch on the receiver section P.C. board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with the
switch on the indoor microcomputer P.C. board.
* However, once the setting is changed, setting to 0001 or
0006 is possible but setting to 0000 requires a setting data
change to 0000 using the wired remote controller
(separately sold) with the normal switch setting (factory
default).
◆
To restore the factory default
To return the DIP switch settings to the factory defaults, set
SW501-1 and SW501-2 to OFF, connect a separately sold
wired remote controller, and then set the data of CODE No.
[5d] to “
0000
” in “External static pressure settings” on this
page.
Setup data
External static pressure
0000
10 Pa
Standard (Factory default)
0001
20 Pa
High static pressure 1
0003
35 Pa
High static pressure 2
0006
50 Pa
High static pressure 3
Setup data
SW501-1
SW501-2
0000
(Factory shipping)
OFF
OFF
0001
ON
OFF
0003
OFF
ON
0006
ON
ON
SW501-1
MCU(IC501)
SW501-2
77-EN
78-EN