Indoor unit power-ON sequence
<Cautions at test run>
s
Power supply/Indoor/Outdoor serial and Gr wiring: OK
s
Powers of all indoor units are turned on within 3 minutes.
s
Reception time for remote controller operation
(After power supply was turned on)
1) When address is OK : Approx. 50 seconds
2) In AUTO address
: Approx. 4 to 5 minutes
Normal
∗
Gr normal
1) There is no duplicated indoor unit address.
2) There is no invalid indoor unit address.
3) Individual unit and master/follower units
are not intermingled.
4) Only a unit for individual.
5) A master indoor unit and 1 or more
follower indoor units for Gr.
<Automatic
address judgment>
<Initial communication>
<Usual regular
communication>
<By feed unit>
Power ON
Gr construction check
System start
Outdoor model distinction (10 seconds) (Indoor unit)
Twin Master/follower distinction (Indoor unit)
Gr construction, louver information (Remote controller)
Remote controller operation is available.
(Approx. 50 seconds after power-ON)
Regular communication between indoor units (Every 30 seconds) (Master/Follower)
Regular communication on the identical pipe (every 30 seconds) (Twin Master/Follower)
(When the above status changes, immediately communicates.)
(Repetition)
s
The unit without power feed waits entirely
→
Waiting status is released by system start
s
Reboot when power is fed on the way
3 minutes elapse
O
N
l
a
m
r
o
n
t
o
N
YES
Automatic address starts.
(Approx. 1 minute up to finish)
s
In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot
receive regular communication from the master unit and regular communication on identical pipe within
120 seconds after power was turned on, it reboots (system reset).
→
The operation starts from judgment of automatic address (Gr construction check) again.
(If the address of the master unit was determined in the previous time, the power fed to the master unit
and reboot works, the master unit may change though the indoor unit line address is not changed.)
–
6
5
–
SVM-13072.indb 74
SVM-13072.indb 74
11/01/13 1:53 PM
11/01/13 1:53 PM
Summary of Contents for RAV-SM304ATJP-E
Page 17: ... 17 FILE NO SVM 14059 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SM304AT P SM404AT P ...
Page 21: ... 21 FILE NO SVM 14059 4 WIRING DIAGRAM 4 1 RAV SM304AT P ...
Page 22: ... 22 FILE NO SVM 14059 4 2 RAV SM404AT P ...
Page 41: ... 41 FILE NO SVM 14059 7 2 Outdoor Print Circuit Board RAV SM304AT P SM404AT P MCC 1656 ...
Page 84: ...FILE NO SVM 14059 13 EXPLODED VIEWS AND PARTS LIST 13 1 RAV SM304ATP E RAV SM304ATP TR 84 ...
Page 86: ...FILE NO SVM 14059 Inverter assembly SM30 86 ...
Page 88: ...FILE NO SVM 14059 13 2 RAV SM404ATP E RAV SM404ATP TR 88 ...
Page 90: ...FILE NO SVM 14059 Inverter assembly SM40 90 ...
Page 92: ...FILE NO SVM 14059 13 3 RAV SM304ATJP E 92 ...
Page 94: ...FILE NO SVM 14059 Inverter assembly SM30 94 ...
Page 96: ...FILE NO SVM 14059 13 4 RAV SM404ATJP E 96 ...