![Toshiba RAV-SM304ATJP-E Service Manual Download Page 67](http://html.mh-extra.com/html/toshiba/rav-sm304atjp-e/rav-sm304atjp-e_service-manual_1135355067.webp)
FILE NO. SVM-1
4059
Setup of line address of outdoor unit,
indoor unit address, and group address
Completion of cabling work
Turn on power of outdoor unit.
Turn on power of outdoor unit.
Connect one remote controller with
one indoor unit (1 : 1) tentatively with
communication cable.
END
Turn on power of outdoor unit.
Set to all indoor units one by one.
Do you arbitrarily set the
indoor unit address?
Do you change setting after
automatic setting at the first time?
Is refrigerant line 1 line?
Is group control performed?
Setup of automatic
address finishes within
4 to 5 minutes.
After completion of address
setup, change is to arbitral
address/group manually.
(To AUTO address mode)
(MANUAL)
( ) (
)
YES
YES
YES
YES
NO
NO
NO
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor
unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address
setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted
while automatic address works. (Approx. 4 to 5 minutes)
s
When the following addresses are not stored in the neutral memory (IC503) on the indoor P.C. board, a test
run operation cannot be performed. (Unfixed data at shipment from factory)
Line address
Indoor unit address
Group address
Item code
12
13
14
Data at shipment
0099
0099
0099
Setup data range
0001 (No. 1 unit) to 0064 (No. 64 unit)
0001 (No. 1 unit) to 0064 (No. 64 unit)
Max. value of indoor units in the identical refrigerant line
0000 : Individual (Indoor units which are not controlled in a group)
0001 : Master unit (1 indoor unit in group control)
0002 : Sub unit (Indoor units other than master unit in group control)
10. ADDRESS SETUP
10-1. Address Setup Procedure
–
6
7
–
SVM-13072.indb 85
SVM-13072.indb 85
11/01/13 1:53 PM
11/01/13 1:53 PM
Summary of Contents for RAV-SM304ATJP-E
Page 17: ... 17 FILE NO SVM 14059 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV SM304AT P SM404AT P ...
Page 21: ... 21 FILE NO SVM 14059 4 WIRING DIAGRAM 4 1 RAV SM304AT P ...
Page 22: ... 22 FILE NO SVM 14059 4 2 RAV SM404AT P ...
Page 41: ... 41 FILE NO SVM 14059 7 2 Outdoor Print Circuit Board RAV SM304AT P SM404AT P MCC 1656 ...
Page 84: ...FILE NO SVM 14059 13 EXPLODED VIEWS AND PARTS LIST 13 1 RAV SM304ATP E RAV SM304ATP TR 84 ...
Page 86: ...FILE NO SVM 14059 Inverter assembly SM30 86 ...
Page 88: ...FILE NO SVM 14059 13 2 RAV SM404ATP E RAV SM404ATP TR 88 ...
Page 90: ...FILE NO SVM 14059 Inverter assembly SM40 90 ...
Page 92: ...FILE NO SVM 14059 13 3 RAV SM304ATJP E 92 ...
Page 94: ...FILE NO SVM 14059 Inverter assembly SM30 94 ...
Page 96: ...FILE NO SVM 14059 13 4 RAV SM404ATJP E 96 ...