– 37 –
Concealed Duct High Static Pressure
Installation Manual
: Lighting
: Flashing
: OFF
: The air conditioner automatically enters the auto-address setting mode.
ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR: Orange GR: Green
P26
ALT
Outdoor unit inverter
Idc activated
Outdoor
IGBT, outdoor unit P.C. board, inverter wiring,
compressor --- Short-circuit protection for compressor
drive circuit devices (G-Tr/IGBT) was activated.
Entire stop
P29
ALT
Outdoor unit position
error
Outdoor
Outdoor unit P.C. board, high-pressure switch ---
Compressor motor position error was detected.
Entire stop
P31
ALT
Other indoor unit error
Indoor
Another indoor unit in the group is raising an alarm.
Entire stop
E03/L07/L03/L08 alarm check locations and error
description
Auto-reset
37-EN