– 19 –
Concealed Duct High Static Pressure
Installation Manual
Thermal insulation process
Apply thermal insulation for the pipes separately
at liquid side and gas side.
For the thermal insulation to the pipes at gas side,
be sure to use the material with heat-resisting
temperature 120°C or higher.
Using the attached thermal insulation material,
apply the thermal insulation to the pipe connecting
section of the indoor unit securely without gap.
REQUIREMENT
• Apply the thermal insulation to the pipe
connecting section of the indoor unit securely
up to the root without exposure of the pipe.
(The pipe exposed to the outside causes water
leak.)
• Wrap heat insulator with its slits facing up
(ceiling side).
Indoor unit
Union
Heat insulation pipe
(Accessory)
Flare nut
Heat
insulator of
the pipe
19-EN