– 49 –
Notification of filter cleaning term setup
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed according to the
condition of installation.
For setup method, refer to “Change of lighting term of filter sign” and “To secure better effect of heating” in the Applicable
controls of this Manual.
In case of wireless type
The sensor of indoor unit with wireless remote controller can receive a
signal 7 m or less.
Based upon it, determine a place where the remote controller is operated
and the installation place of the indoor unit.
• To prevent a malfunction, select a place where is not influenced by a
florescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with wireless remote
controller can be installed in the same room.
7
m
or
le
ss
4
Installation
WARNING
• Install the air conditioner certainly to sufficiently withstand the weight.
• If the strength is insufficient, the unit may fall down resulting in human injury.
• Perform a specified installation work to guard against strong wind or earthquake.
• An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use
buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
External view
(Unit:mm)
511
67
67
910
372
359
422
502
103
31
163
33
40
21
803
57
210
845
168
21
21
21
120
805
19
645
168
20
80
59
80
4-Ø4
Ø92
(inside)
Air filter
Refrigerant piping
Fresh air intake
(knock-out hole)
(i
ns
ide)
Drain-up port
Hung-up plate
97-EN