CN51
CN40
SW01
Remote controller
Indoor control
P.C. board
1:1 model
connection interface
communication circuit
Terminal
resistance
1:1 model connection interface
P.C. board
MCC-1440
Indoor unit
1:1 model
connection interface
Communication units
: Total 64 units
Communication distance : 2000 m
CN50
CN41
Terminal block
(A, B)
Central controller
Indoor units in all refrigerant lines: Max. 64 units
[If mixed with SMMS (Link wiring), multi indoor units are included.]
* However group follower units of SDI, DI series are not included in number of the units.
Central control device
U1
U3
U2
U4
Central control device
U1
U3
1 2 3
U2
U4
Central control devices: Max. 10 units
Refrigerant line 1
Outdoor unit
Indoor unit
1 2 3
Refrigerant line 2
1 2 3
Refrigerant line 3
1 2 3
Refrigerant line 4
1 2 3
A B
U3 U4
Caution 3
1 2 3
A B
U3 U4
1 2 3
A B
1 2 3
A B
1 2 3
A B
1 2 3
A B
U3 U4
1:1 model connection
interface
This product
sold separately
( )
Caution 1
Remote controller
Indoor/outdoor inter-unit wire (AC230V serial)
Central control system wiring
Header unit
Header
unit
Follower
unit
Follower
unit
Follower
unit
* Wiring for No.1 and 2 only
Caution 2
Remote controller
Remote controller
Remote controller
Remote controller
wiring
)
e
l
p
i
r
t
f
o
e
l
p
m
a
x
E
(
n
o
i
t
a
r
e
p
o
e
l
p
i
r
T
/
n
i
w
T
)
s
t
i
n
u
8
.
x
a
M
(
n
o
i
t
a
r
e
p
o
p
u
o
r
G
Model name: TCB-PCNT30TLE2
8-2-1. 1:1 Model Connection Interface (TCC-LINK adapter)
1. Function
This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface.
2. Microprocessor block diagram
3. 1:1 model connection interface wiring connection
CAUTION
1) When controlling DI, SDI series collectively, 1:1 model connection interface (This option) is required.
2) In case of group operation, twin-triple operation, the 1:1 model connection interface is necessary to be con-
nected to the header unit.
3) Connect the central control devices to the central control system wiring.
4) When controlling DI, SDI series only, turn on only Bit 1 of SW01 of the least line of the system address No. (OFF
when shipped from the factory)
∗∗∗∗∗
In case of DI, SDI series, the address is necessary to be set up again from the wired remote
controller after automatic addressing.
8-2. Setup at Local Site / Others
FILE NO. SVM-18038