64
4.
SPECIFICATIONS OF ELECTRICAL PARTS
No
PARTS NAME
TYPE
SPECIFICATIONS
Compressor
Outdoor Unit fan motor
Running capacitor for
outdoor fan motor
Magnetic contactor
(Supplier: Fuji Electric)
High pressure switch
Solenoid coil for four-way valve
Crankcase heater
Sensor for defrosting
Fuse
Sensor for cooling operation in low
ambient temperature
Solenoid coil for two-way valve
Running capacitor
for compressor
Transformer (Outdoor Unit)
Bimetal thermostat
1
2
3
4
5
6
7
8
9
10
11
12
13
14
RAV-164AH-PE
˚
C
-12
10
k
Ω
67.5
21.3
˚
C
-12
10
k
Ω
67.5
21.3
PG350X3F-4LS
SMF-230-39N-2
FMCa-1S-02
ACB-2TB04W
CHV-AC240V
NEV AC 240V
FT-67
CS-12A
Output (rated) 1.5kW, 2 pole, 220/240V, 1 Phase, 50Hz
Winding Resistance: Common Run 1.17
Ω
at 20
˚
C
Common Start 2.34
Ω
at 20
˚
C
Output (rated) 39W, 6 pole, 230V, 1 Phase, 50Hz
Winding Resistance: Common Run (Blk-Red) 97.1
Ω
at 25
˚
C
Common Start (Blk-White) 97.5
Ω
at 25
˚
C
AC 400V, 4µF
AC 220-240V, 50Hz
Tripping pressure 30kgf/cm
2
G
Resetting pressure 23kgf/cm
2
G
AC 220-240V
AC 240V, 28W
Maximum input
15.5mA
T5A
Maximum input
15.5mA
AC 220-240V, 50Hz
AC 440V, 45µF
AC 187-264V
Tripping temperature: 110
˚
C
Resetting temperature: 90
˚
C
4.31
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807