No.
Part name
Procedures
Remarks
1. Detachment
1) Perform work of item 1 of
1
and 1 of
2
.
Requirement:
Perform the work on a corrugated
cardboard, cloth, etc. to prevent
scratches to the product.
2) Remove the front cabinet, and place it
down so that the fan guard side faces
downwards.
3) Remove the hooking claws by pushing a
minus screwdriver according to the arrow
mark in the right figure, and remove the
fan guard.
2. Attachment
1) Insert the claws of the fan guard in the
hole of the front cabinet. Push the hooking
claws (8 positions) by your hand and fix
the claws.
Requirement:
This completes all the attaching
work. Check that all the hooking
claws are fixed to the specified
positions.
Fan guard
Minus screwdriver
Hooking claw
6
Pulse Modulating
Valve coil
7
1. Detachment
2. Attachment
1) Insert the coil at position which
perpendicular with pipe of PMV then turn
the coil
by 180 degrees
.
Make sure that lead wire of coil
is opposite with pipe of PMV
1)
Perform work of item 1 of
1
and 1 of
2
and
3
.
2)
Turn the coil by
180
degrees then
remove
by pull it upward.
BODY-PMV
COIL-PMV
Rotate 180°C
FILE NO. SVM-18006
- 108 -