6

CAUTION

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

 • 

Projection margin in 

fl

 aring : A (Unit : mm)

Rigid (clutch type)

Obliquity

Roughness

Warp

90

Imperial (wing nut type)

Outer dia. of copper pipe

R410A

Ø6.35

1.5 to 2.0

Ø9.52

1.5 to 2.0

Ø12.70

2.0 to 2.5

Die

Pipe

A

Align the centers of the connecting pipes and tighten the 

fl

 are nut as far as pos-

sible with your 

fi

 ngers. Then tighten the nut with a spanner and torque wrench 

as shown in the 

fi

 gure.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

Ø6.35 mm

16 to 18 (1.6 to 1.8 kgf·m)

Ø9.52 mm

30 to 42 (3.0 to 4.2 kgf·m)

Ø12.70 mm

50 to 62 (5.0 to 6.2 kgf·m)

Evacuating

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

Outer dia.

of copper pipe

R410A tool used

Conventional tool 

used

Ø6.35

0 to 0.5

1.0 to 1.5

Ø9.52

0 to 0.5

1.0 to 1.5

Ø12.70

0 to 0.5

1.0 to 1.5

Use a wrench to secure.

Use a torque wrench to tighten.

Flare nut

Half union

Internally
threaded side

Externally
threaded side

• 

Tightening torque of 

fl

 are pipe connections

Flare at
indoor unit side

Flare at
outdoor unit side

 

The operating pressure of R410A 
is higher than that of R22 (approx. 
1.6 times). It is therefore necessary 
to 

fi

 rmly tighten the 

fl

 are pipe 

connecting sections (which connect 
the indoor and outdoor units) up to the 
speci

fi

 ed tightening torque. Incorrect 

connections may cause not only a 
gas leakage, but also damage to the 
refrigeration cycle.

1.  How to shape the pipes 
 

Shape the pipes along the incused line on 
the outdoor unit.

2. How to 

fi

 t position of the pipes

 

Put the edges of the pipes to the place with 
a distance of 85 mm from the incused line.

     Shaping pipes

Incused line

     Flaring

Be sure to use a vacuum pump with counter-

fl

 ow prevention function so that 

inside oil of the pump does not 

fl

 ow backward into pipes of the air conditioner 

when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A, 
refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 25 meters. (15 minutes for 25 meters) 
(assuming a pump capacity of 27 liters per minute) Then con

fi

 rm that the 

compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

     Using a vacuum pump

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

fl

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

•  Open the valve stem all the way out, but do not try to open it beyond the 

stopper.

•  Securely tighten the valve stem cap with torque in the following table:

     Packed valve handling precautions

m

m

 

4

The hexagon wrench
is required.

Gas side
(Ø12.70 mm)

50 to 62 N·m
(5.0 to 6.2 kgf·m)

Gas side
(Ø9.52 mm)

30 to 42 N·m
(3.0 to 4.2 kgf·m)

Liquid side
(Ø6.35 mm)

16 to 18 N·m
(1.6 to 1.8 kgf·m)

Service port

9 to 10 N·m
(0.9 to 1.0 kgf·m)

CAUTION

• 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.

1110251240-EN.indd   6

1110251240-EN.indd   6

4/19/11   2:07:21 PM

4/19/11   2:07:21 PM

Summary of Contents for RAS-16SAVP2 Series

Page 1: ...AL Indoor unit RAS 10 13 16SKVP2 Series RAS 25 35 45SKVP2 Series Outdoor unit RAS 10 13 16SAVP2 Series RAS 25 35 45SAVP2 Series 1110251240 ENGLISH PУCСКИЙ TÜRKÇE Cover 1110251240 indd 1 Cover 1110251240 indd 1 4 5 11 5 19 47 PM 4 5 11 5 19 47 PM ...

Page 2: ...onte edilmesi 4 İç Ünitenin Takılması 5 Su Boşaltma 5 DIŞ ÜNİTE 5 Montaj Yeri 5 Soğutma Maddesi Boru Bağlantısı 6 Boşaltma 6 Kablo Bağlantısı 7 DİĞERLERİ 7 Gaz Kaçağı Testi 7 Uzaktan Kumanda ile A B Seçimi 7 Test İşlemi 7 Otomatik Yeniden Başlama Ayarı 7 İÇİNDEKİLER TR MEPЫ БEЗOПACHOCTИ 1 СХЕМА УСТАНОВКИ ВНУТРЕННЕГО И НАРУЖНОГО БЛОКОВ 2 Oпционaльныe Уcтaновочныe Чacти 2 BHУTPEHHИЙ БЛOК 3 Mecто Уcт...

Page 3: ...ting machine oil the sizes of charging port connecting sections on the main unit are different from those for the conventional refrigerant and different size tools are also required For connecting pipes use new and clean piping materials with highpressure withstand capabilities designed for R410A only and ensure that water or dust does not enter Moreover do not use any existing piping as its press...

Page 4: ...hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Batteries Pan head wood screw Remote control holder Vinyl tape Apply after carrying out a drai...

Page 5: ...es near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote...

Page 6: ...n cut them with a pair of nippers or an equivalent tool Slit Slit Left hand connection with piping Bend the connecting pipe so that it is laid within 43 mm above the wall surface If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend the ...

Page 7: ...TE The hole should be made at a slight downward slant on the outdoor side 50 mm or more Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch Do not form the drain hose into a wavy shape Do not rise the drain hose Extension drain hose Inside the room Drain hose Shield pipe Arrange the drain pipe for proper drainage from the unit Improper drainage can result i...

Page 8: ...e Flaring Be sure to use a vacuum pump with counter flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops If oil inside of the vacuum pump enters the air conditioner which use R410A refrigeration cycle trouble may result 1 Connect the charge hose from the manifold valve to the service port of the packed valve at gas sid...

Page 9: ...6 1 5 mm2 or more NOTE Connecting cable Wire type More than H07RN F or 245 IEC66 1 0 mm2 or more Wrong wiring connection may cause some electrical parts burn out Be sure to comply with local cords on running the wire from indoor unit to outdoor unit size of wire and wiring method etc Every wire must be connected firmly This installation fuse 15A must be used for the power supply line of this air c...

Page 10: ...Cover back 1110251240 indd 1 Cover back 1110251240 indd 1 4 5 11 5 19 32 PM 4 5 11 5 19 32 PM ...

Reviews: