– 50 –
FILE NO. SVM-02001
PRESET
FAN
MODE
Hi-POWER
ON
OFF
SET
CLR
ECO
AUTO
TIMER
CLOCK CHECK
RESET
FILTER
FIX
SWING
MEMO
START/STOP
A
B
AUTOA
SET
CLR
CLOCK CHECK
RESET
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to H in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service mode,
the indoor controller diagnoses the operation
condition and indicate the information of the self-
diagnosis on the display of the remote control with
the check codes. If a fault is detected, all lamps on
the indoor unit will blink at 5Hz and it will beep for
10 seconds (Pi, Pi, Pi....). The timer lamp usually
blinks (5Hz) during the self-diagnosis.
9-4-1. How to use Remote Control in Service Mode
(1) Press [CHECK] button with a tip of pencil to set the
remote control to the service mode.
•
“00” is indicated on the display of the remote
control.
•
The timer lamp on the indoor unit blinks continu
ously. (5 times per 1 sec.)
•
Alphanumeric characters are used for the check code.
is 5.
is 6.
is A.
is B.
is C.
is D.
* This illustration is only for RAS-13UKHP-E,
RAS-10UKHP-E and
RAS-07UKHP-E
(2) Press [TIMER
8
] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote control
will change as follows:
;
00
;
01
;
02 ··· 1d
;
1E
;
22
•
Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
•
Press [TIMER
9
] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
•
2-digits alphanumeric will be indicated on the
display.
•
All lamps on the indoor unit will blink. (5 times per
1 sec.)
(3) Press [START/STOP] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.