– 17 –
FILE NO. SVM-02001
5-3. RAS-10UKHP-E / RAS-10UAH-E
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH120T1-4C
Cooling
Heating
Mark( )means check points of Gas Leak.
O.D.:9.52mm
O.D.:6.35mm
Cooling
Heating
Packed valve
(
∅
9.52)
Packed valve
(
∅
6.35)
0.39m
(Connecting pipe)
∅
9.52
0.49m
(Connecting pipe)
∅
6.35
T1
P
Refrigerant
R-22 : 0.74 kg.
Capillary tube
∅
1.7x1600
Accumulator
Evaporator
Standard
1.55
40.0
High
20/–
7/6
Heating
Overload*1
1.9 ~ 2.1
52.0 ~ 59.0
Low
27/–
24/18
Low temperature
1.3
35.0
High
20/–
–10/–10
Standard
1.94
12.0
High
27/19
35/24
Cooling
Overload
2.50
15.0
High
32/23
43/26
Low temperature
0.32
2.0
Low
21/15
21/15
Note
:
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1
• During heating overload operation, a value for the high temperature limit control operation is included.
50Hz
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor