User’s Manual
65
2. Expanded Functions
TOSLINE-S20LP
Station No. 3
T3H
T3H
(self-station)
(target-station)
RW100
D1000
RW101
D1001
RW227
D1127
When R0020 is ON, 128 words data starting with RW100 is transferred to D1000 and after of the T3H on
which station No. 3 S20LP is installed.
When the operation is completed, the status is set in RW050 and instruction output comes ON.
Note
•
Keep the input ON until the output comes ON.
•
This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON)
(1) Target station No. is invalid. (for S20LP)
(2) Invalid register designation. (In case of T and C registers, T
→
T and C
→
C is only possible)
(3) Source/destination register address range is out of valid range.
(4) Destination register is write-protected.
(5) Response time-out is occurred.
(6) If expanded F register is designated;
- when MMR setting is not made.
- when IC card is not installed.
- when IC card is used to store program.
- when IC card is write-protected. (for destination)
•
By using SW067, register write-protect is available against SEND instruction of other T3H.
F 9 8 7 6 5 4 3 2 1 0
SW067 SW
C
T
F
D
RW
LW
W
YW
0: Write enable
1: Write protect
•
Resetting the status register (operand
B
) is necessary at the first scan.
•
When using the TOSLINE-S20LP or Ethernet module (EN311), read the manual for these network
modules.
Both F register in CPU and
expanded F register in IC card