2. Expanded Functions
Expanded file register data Write [MW]
Request message format (Host
→
T3H):
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
( A
ADR
M W
Starting register
,
Bank
,
N
,
Data #1
Can be shortened
n-5
n-4
n-3
n-2
n-1
n
,
Data #N-1
,
Data
#N
&
Sum
)
CR
Can be shortened
Can be omitted
ADR:
Station address ... 01 to 32
Starting register:
For 8 k words per bank ..... F0000 to F8191
For 64 k words per bank ... f0000 to f65535 (bank 1)
f0000 to f57343 (bank 2)
Bank:
For 8 k words per bank ..... 1 to 15
For 64 k words per bank ... 1 to 2
N:
Number of registers to be written ... 1 to 46 (see Note)
Data:
Data in hexadecimal
Sum:
Check
sum
Response message format (T3H
→
Host):
1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
( A
ADR
S T
Status
&
Sum
)
CR
Status:
T3H operation status
Upper case F
Lower case f