P9 ASD Installation and Operation Manual
161
Tension Torque Bias Input
Program
Torque
Torque Control
This parameter
Enables/Disables
the
Tension Torque Bias
input function.
This feature is enabled by selecting a
Tension Torque Bias
input signal source.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Direct Access Number — F423
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Load Sharing Gain Input
Program
Torque
Torque Control
This parameter
Enables/Disables
the
Load Sharing Gain
input function.
This feature is enabled by selecting a
Load Sharing Gain
input signal source.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Direct Access Number — F424
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Forward Speed Limit Input
Program
Torque
Torque Speed Limiting
This parameter
Enables/Disables
the
Forward Speed Limit Input
control
function. When enabled and operating in the
Torque Control
mode, the
forward speed limit is controlled by the input selected here.
If
Setting
Forward Speed Limit
input.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F425
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes