P9 ASD Installation and Operation Manual
Forward Speed Limit Level
Program
Torque
Torque Control
This parameter provides a value to be used as the
Forward Speed Limit
setting
if the
F426 setting
Direct Access Number — F426
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (
Units — Hz
Reverse Speed Limit Input
Program
Torque
Torque Control
This parameter
Enables/Disables
the
Reverse Speed Limit Input
control
function. When enabled and operating in the
Torque Control
mode, the reverse
speed limit is controlled by the terminal selected here. If
Setting
is selected, the
value set at
is used as the
Reverse Speed Limit
input.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F427
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Reverse Speed Limit Input Level
Program
Torque
Torque Control
This parameter provides a value to be used as the
Reverse Speed Limit
setting
if the
F428 setting
Direct Access Number — F428
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (
Units — Hz
Speed Limit (torque=0) Center Value Reference
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets the input signal source or value that will be used to control the
allowable speed variance.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —
(
Setting)
Direct Access Number — F430
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes