– 11 –
HWM: Hot Water Module
Sample 2.
HWM: Hot Water Module
Sample 3.
HWM
Isolating
valve
Air vent valve
Isolating
valve
Strainer
(30 to 40
meshes)
Isolating
valve
Pump
Procured locally
Auxiliary heat
source
Booster
Heater
Direct Buffer Tank
for Space Heating
Line
Heater
Crucial
heat
source
Isolating
valve
For heating applications
(Fan coils, radiators, under
floor)
Within 5 m
Expansion vessel
Pressure relief valve
Set: 0.3 MPa
Valve for filling and
draining water
HWM
Isolating
valve
Air vent valve
Isolating
valve
Strainer
(30 to 40
meshes)
Isolating
valve
Pump
Procured locally
Auxiliary
heat source
Line
Heater
Crucial
heat
source
Isolating
valve
Cold water feed
Heater
Sanitary hot water use
Indirect Sanitary
Hot Water Tank
Within 5 m
Expansion vessel
Pressure relief valve
Set: 0.3 MPa
Valve for filling and
draining water
21-EN
22-EN
Summary of Contents for MMW-AP0481CHQ-E