3. Data display of outdoor cycle (Displayed on each outdoor unit)
SW01
1
SW02
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SW03
2
Display contents
Pd pressure data
Pd pressure (MPaG) is displayed with decimal data.
(MPaG: Approx. 1/10 value of kg/cm
2
G data)
Ps pressure data
Ps pressure (MPaG) is displayed with decimal data.
PL pressure conversion data Estimated pressure of liquid line (MPaG) is displayed with decimal data.
TD1 sensor data
Temperature sensor data (°C) is displayed
with decimal notation.
TD2 sensor data
• Symbol display for 1 sec. and data display for 3 sec. are
alternately displayed.
TS1 sensor data
• Data is displayed in [
∗
].
• Negative data is displayed as [–
∗
∗
∗
∗
].
TS2 sensor data
TE sensor data
TL sensor data
TO sensor data
TK1 sensor data
TK2 sensor data
TK3 sensor data
TK4 sensor data
—
A
—
B
—
—
A
—
B
A
B
P d.
∗
.
∗
∗
P S.
∗
.
∗
∗
P L.
∗
.
∗
∗
Symbol
t d
1
1 1
Data
∗
∗
∗
.
∗
Symbol
t d
2
1 1
Data
∗
∗
∗
.
∗
Symbol
t S
1
1 1
Data
∗
∗
∗
.
∗
Symbol
tS
2
1 1
Data
∗
∗
∗
.
∗
Symbol
tE
—
Data
—
—
Symbol
t L
Data
∗
∗
∗
.
∗
Symbol
t o
Data
∗
∗
∗
.
∗
Symbol
F 1
Data
∗
∗
∗
.
∗
Symbol
F 2
Data
∗
∗
∗
.
∗
Symbol
F 3
Data
∗
∗
∗
.
∗
Symbol
F 4
Data
∗
∗
∗
.
∗
4. Data display of indoor unit information (Displayed on the header unit only)
SW01
4
5
6
7
8
9
10
11
12
13
SW02
1 to 16
SW03
1 to 3
Display contents
Receiving status of
B
Receiving time: [… … 1], Not received: [… … …]
indoor BUS communication
Indoor check code
B
No check code: [– – –]
Indoor capacity
B
0. 2, 0. 5, 0. 8, … 1, 1. 2, 1. 7, … 2, 2. 5, … 3, 3. 2, … 4, … 5,
(HP) horse power
… 6, … 8, 1 0, 1 6, 2 0
Indoor request command
B
Data is displayed with Hexadecimal notation [… … 0 to … … F] : Heating
(S code)
Indoor PMV opening data
B
Data is displayed with Hexadecimal notation
Indoor TA sensor data
B
Data is displayed with Hexadecimal notation
Indoor TF sensor data
B
Data is displayed with Hexadecimal notation
Indoor TCJ sensor data
B
Data is displayed with Hexadecimal notation
Indoor TC1 sensor data
B
Data is displayed with Hexadecimal notation
Indoor TC2 sensor data
B
Data is displayed with Hexadecimal notation
NOTE) Indoor address No. is chosen by changing SW02 and SW03.
SW03
1
2
3
SW02
1 to 16
1 to 16
1 to 16
Indoor address
SW02 setup number
SW02 setup 16
SW02 setup 32
7-segment display A
[01] to [16]
[17] to [32]
[33] to [48]