– 40 –
DN
Item
Description
At shipment
Fd
Priority operation mode
(FS unit)
0000: Heating
0001: Cooling
0000: Heating
FE FS unit address
0001 : No.1 unit to 0064 : No.64 unit
0099 : Unfixed
0099: Unfixed
F6
Presence of Application
control kit
(TCB-PCUC1E)
0000: None
0001: Exist
0000: None
D0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid
E6
Wireless remote
controller A-B selection
0000: A
0001: B
0000: A
B7
Occupancy sensor
operation at absent time
0000: Stand by
0001: operation stop
0000: Stand by
F0 Swing mode
0001 : Standard
000
3
: Cycle swing
0002 : Dual swing
0001: Standard
F1
Louver fixed position
(Louver No.1)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F2
Louver fixed position
(Louver No.2)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F
3
Louver fixed position
(Louver No.
3
)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed
F4
Louver fixed position
(Louver No.4)
0000 : Release
0005 : Downward discharge position
0001 : Horizontal discharge position 0000: Not fixed