– 39 –
Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Description
At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
000
3
: 5000H
0002 : 2500H
02
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
1E
Temp difference of
[AUTO] mode selection
COOL
→
HEAT,
HEAT
→
COOL
0000: 0 deg
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0010: 10 deg
to
000
3
:
3
deg
(Ts ±1.5)
06
Heating temp shift
0000: 0 °C
0002: +2 °C
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
to
0002 : +2°C
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
2A
Selection of option/Trouble
input (TCB-PCUC1E: CN
3
)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
28
Automatic restart of
power failure
0000: None
0001: Restart
0000: None
14
Group address
0000: Individual
0002: Follower unit of group
0001: Header unit of group
0099: Unfixed
19
Louver type
(Air direction adjustment)
0000: No louver
0004: (4-way Air Discharge Cassette type)
0001: Swing only
0004: (4-way Air
Discharge Cassette
type)
11
Indoor unit capacity
0000: Unfixed
0001 to 00
3
4
According to capacity
type
12 Line address
0001: No.1 unit
00
3
0: No.
3
0 unit
to
0099: Unfixed
3
2 TA sensor selection
0000: Body TA sensor
0001: Remote controller sensor
0000: Body TA sensor
33
Temperature unit select 0000: °C (at factory shipment)
0001: °F
0000: °C
3
1 Ventilating fan control
0000: Unavailable
0001: Available
0000: Unavailable
B
3
Soft cooling
0000: Unavailable
0001: Available
0001: Available
77 Dual set point
0000: Unavailable
0002: Available
0000: Unavailable
1
3
Indoor unit address
0001: No.1 unit
0064: No.64 unit
to
0099: Unfixed
Type
10
0014 : Compact 4-way Cassette
0014 : Compact
4-way Cassette
0F
Cooling only
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
04
Specific indoor unit
priority
0000: No priority
0001: Priority
0000: No priority
0
3
Central control address 0001: No.1 unit
0099: Unfixed
0064: No.64 unit
to
0099: Unfixed
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable
(cannot be performed)
0000: Available
B5
Occupancy sensor/
Wireless A-B selection
Provided/None
0000: None
0002: Wireless remote controller provided
0001: Occupancy sensor provided 0000: None
B6
Occupancy sensor
Enable/Invalid
(Absence time judgment
time)
0000: Invalid
0002: 60min.
0005; 150min.
0001:
3
0min.
0004; 120min.
0002: Enable
(60 min.)
5d
High-ceiling adjustment
(Air flow selection)
0000: Standard
SET
DATA
Type
AP005 to
AP012
AP015
AP018
0000
Standard (factory default)
2.7 m or less
2.9 m or less
3.5 m or less
0001
High-ceiling (1)
—
3.2 m or less
—
0003
High-ceiling (3)
—
3.5 m or less
—