– 68 –
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
H08
H08
01: TK1 sensor
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
I/F
Error in
temperature
sensor for oil level
detection
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK1 sensor
connector.
• Check resistance characteristics of
TK1 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK2 sensor
connector.
• Check resistance characteristics of
TK2 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK3 sensor
connector.
• Check resistance characteristics of
TK3 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK4 sensor
connector.
• Check resistance characteristics of
TK4 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK5 sensor
connector.
• Check resistance characteristics of
TK5 sensor.
• Check for defect in outdoor P.C.
board (I/F).
H14
H14
—
I/F
Compressor 2
case thermo
activation
All stop
Compressor 2 case thermo
was activated.
• Check Compressor 2 case thermo
circuit.
(Connector, Wiring, Circuit board)
• Open and check the service valve.
(Gas side, Liquid side)
• Check the outdoor PMV clogging
(PMV1, 2).
• Check the SV42 circuit.
• Check the SV4 circuit (SV41 / 42
miswiring).
• Check the opening status of indoor
PMV.
• Check the 4-way valve error.
• Check the refrigerant shortage.
H15
H15
—
I/F
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Air discharge temperature of
(TD2) does not increase
despite compressor 2 being in
operation.
• Check installation of TD2 sensor.
• Check connection of TD2 sensor
connector and wiring.
• Check resistance characteristics of
TD2 sensor.
• Check for defect in outdoor P.C.
board (I/F).
Outdoor 7-segment display
Check
code
Sub-code
Main
remote
controller