– 44 –
How to change an indoor unit address by using a wired remote control
Use this method to change the address of indoor units (one to one or group control) that have had the original
address set automatically.
This procedure must be done while the units are not operating.
1
Simultaneously push and hold the “SET ”, “CL ”, and “TEST ” buttons for more
than 4 seconds. If there are 2 or more units in a group, the first “UNIT No.” indicated is the
header unit.
Ø
2
Push
UNIT LOUVER
button (button of left side) repeatedly to select an indoor unit address to
change. If 2 or more units are controlled in a group the fan of the selected unit will be
energized.
Ø
3
Push the TEMP.
/
buttons repeatedly to select
13
13
13
13
13
for CODE No.
Ø
4
Push the TIME
/
buttons repeatedly to change the value indicated in the SET DATA
section.
Ø
5
Push the “SET ” button, to save address.
Ø
6
Push
UNIT LOUVER
” button (button of left side) repeatedly to select another indoor unit addresses
to change. Repeat steps 4 through 6 to continue changing indoor unit address and make
each of them unique.
7
Push
UNIT LOUVER
button (button of left side) to review/confirm the revised addresses.
Ø
8
If the addresses have been changed correctly, push the “TEST ” button to finish the
procedure.
TEMP.
ON / OFF
TIME
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
CODE No.
UNIT No.
R.C.
No.
TIMER SET
MODE
FAN
SET DATA
SETTING
00 00
-
1
10
3
5
8
1
4
2, 6, 7
Fin