– 36 –
Function Select Item No. (DN) Table
(Indicates items necessary to perform the applicable control at local site)
DN
01
02
03
04
0d
0F
10
11
12
13
14
28
2E
31
C8
Item
Filter sign lighting time
Filter dirty degree
Central control address
Priority to specific indoor
air conditioner
Cooling/Heating AUTO
mode provided / None
Cooling only
Type
Indoor air conditioner
capacity
Line address
Indoor air conditioner
address
Group address
Automatic reset of power
failure
HA terminal (T10)
selection
Fan (Single operation)
Outside Air Unit
Contents
0000: None
0001: 150H
0002: 2500H
0003: 5000H
0004: 10000H
0000: Standard
0001: Heavy dirt (Half of standard time)
0001: No.1 unit ~ 0064: No.64 unit
0099: Undefined
0000: No priority
0001: Priority
0000: AUTO Cooling/Heating provided
0001: No AUTO Cooling/Heating
(Automatic selection by connected outdoor unit)
0000: Heat pump
0001: Cooling only (No [AUTO] [HEAT] display)
0000: (1-way Air Discharge Cassette Type)
0001: (4-way Air Discharge Cassette Type)
~ 0037
0000: Undefined
0001 ~ 0034
0001: No.1 unit ~ 0028: No.28 unit
0001: No.1 unit ~ 0064: No.64 unit
0000: Single
0001: Group master
0002: Group follower
0000: None
0001: Provided
0000: Normal (JEMA)
0001: Card input (shuffling omission)
0000: Unavailable
0001: Available
0000: Undefined
0001: Mixed
At shipment from factory
0002: 2500H
0000: Standard
0099: Undefined
0000: No priority
0001: No AUTO
Cooling/Heating
0000: Heat pump
0016: Outside Air Unit
According to capacity type
0099: Undefined
0099: Undefined
0099: Undefined
0000: None
0000: Normal
(HA terminal)
60
Timer setting
(wired remote control)
0000: Available (can be performed)
0001: Unavailable (cannot be performed)
0000: Available
92
Outside interlock
release condition
0000: Operation stop
0001: Release com munica tion signal receive
0000: Operation stop
0000: Unavailable
0001: Mixed