08: Out of step
0A: IDC
activation
0E: Sync error
0F: Control error
06: Maximum
rotation
exceeded
04: Rotation
difference error
0D: Lock
0C: Fan lock
PDU
Outdoor fan
IPDU error
All stop
(Sub code: 08)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
Check the fan motor.
Check the connector
connection for fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 0A)
FAN IPDU overcurrent
protection circuit
Overcurrent was detected
when the fan started running
or during operation.
Check the fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 0E)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
Check the fan motor.
Check the connector
connection for fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 0F)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
Check the fan motor.
Check the connector
connection for fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 06)
External factors such as
blast
Position detection is not
performed properly.
(Restarted in 6 seconds)
Check the fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 04)
External factors such as
blast
The difference between
targeted rotation and actual
rotation is 25% or more.
(Restarted in 6 seconds)
Check the fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 0D)
FAN IPDU position detection
circuit
Position detection is not
performed properly. (No
wind)
Check the fan motor.
Check the connector
connection for fan motor.
Check the error of IPDU
board for fan.
All stop
(Sub code: 0C)
External factors such as
blast
Position detection is not
performed properly. (Wind
blows) (Restarted in 6
seconds)
Check the fan motor.
Check the error of IPDU
board for fan.