10
1. DESIGN METHODS
1-1. System Overview
1-1-1. Outdoor Units
Corresponding HP
Model name
Heat pump (50Hz)
Heat pump (60Hz)
Cooling capacity (kW)
∗
1
Heating capacity (kW)
∗
1
No.of connectable indoor units
Inverter unit
4HP
5HP
6HP
MCY-MAP0401HT
MCY-MAP0501HT
MCY-MAP0601HT
MCY-MAP0401HT2D
MCY-MAP0501HT2D
MCY-MAP0601HT2D
12.1
14.0
15.5
12.5
16.0
18.0
6
8
9
∗
1 Rated conditions
Cooling:Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating:Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Allocation standard of model name
No mark : Power supply specification, 1Ø/220/230/240V (50Hz)
2D
: Power supply specification, 1Ø/220V, 60Hz
T : Inverter unit
H : Heat pump
Development number
Capacity rank HP × 10
R410A
M : Individual unit
Multi Compact type
MCY- M AP
H T 2D