Domestic Hot Water Heat Pump Service Manual
53
10.1.4 Functions
The functions are similar to the modes of operation but they cannot be accessed directly
from the home view and they can vary from unit to unit
In addition, since SOLAR, FLOOR and COOLING (called extra functions) cannot be used
simultaneously, the choice of these functions should be made from the Installer menu (D26
Extra function). In the function menu, only one of these extra functions is normally shown.
The function menu is described in the following table.
Code
Set point
name
Description
Range
Factory
setting
B1
Ventilation
OFF
The fan switches off when the heat pump does not run.
OFF/
Single
Speed/
2Speeds
OFF
Single
speed
The fan is always running at a single fixed speed (B2 Fan speed), both
when the heat pump is operating and when it is not.
2 Speeds
The fan is always in operation but it runs normally at a higher speed D6
(Fan AUTO Speed) when the heat pump starts operating and at (B2 Fan
speed) when it is not operating.
B2
Fan speed
The main fan speed regulation for the ventilation function. There are three
ventilation level that can be selected: LOW D5 (Min Fan Speed), MEDIUM
D4 (Fan medium speed) HIGH D3 (Max fan speed).
LOW/
MEDIUM/
HIGH
HIGH
B3
Low Tariff
Standard
The low tariff allows the electric heater and the heat pump to run only
during periods with low electricity prices, according to the menu item that
regulate the program of the low tariff D17/ D18 (Low tariff
weekday/weekends). The unit runs only during pre-defined hours of the
day.
If the PV function (B5) is active, this allows the electric heater and the heat
pump to run outside the low tariff period.
OFF/
Standard/
Optimal 1/
Optimal 2
OFF
Low Tariff
Optimal 1
This function allows the maximum exploitation of the lower electricity price
during the night periods between 00:00 and 05:00
Low Tariff
Optimal 2
This function allows the maximum exploitation of the lower electricity price
during the night periods between 00:00 and 05:00.
During the day, the unit works according to Low Tariff periods D17 and
D18
B4
Hot on time
The unit can be programmed to deliver hot water from 1 to 30 days from
the moment in which the function is activated and the HOLIDAY mode is
selected. The unit switches to AUTO MODE in the desired number of
days. If OFF is selected, the function is not active.
OFF/ON
OFF