Domestic Hot Water Heat Pump Service Manual
51
Class
Code
Menu Item
Description
I
I10
MWh th
The total calculated hot water production is displayed in
MWh since last Reset All
I11
EL MWh
The electricity consumption of the electric resistance in
MWh since last Reset All
R
R1
Extra
The operation of the extra relay, for example for the operation of a circulation
pump
R2
Defrost
The operation of the relay that controls the solenoid valve for the defrosting
function is shown
R3
Fan
The fan speed is shown in %
R4
HP
The operation of the compressor is shown
R5
EL
The electric heater operation is shown
Er
Er1
BT1 Error
The temperature sensor BT1 is out of range
Er2
BT2 Error
The temperature sensor BT2 is out of range
Er3
BT3 Error
The temperature sensor BT3 is out of range. If BT3 Error occurs, the unit does not heat
the water in any way
Er4
BT4 Error
The temperature sensor BT4 is out of range. The error Er4 is ignored and the unit runs
normally
Er5
BT5 Error
The temperature sensor BT5 is out of range. The error Er5 is ignored and the unit runs
normally
Er6
Err HP
The pressure switch opens, when the pressure in the heating circuit is above the limit of
pressure specified on the high pressure switch
Er7
Err Evap
The temperature sensor BT2 is above BT1 - 2°C for more than one hour
Er8
Err C Evap
The temperature BT2 is below - 25°C
Er9
Err H Evap
The temperature BT2 is above D11 (Evaporator T max)
Er10
Filter
Replace filter. The alarm is displayed on the main screen, but the operation of the unit is
not affected.
*Optional
10.1.2 Mode of operation
Different strategies to heat the water can be selected from the main control panel pressing 5 or
6 (Scroll down or scroll up) from the home view.
The possible modes of operation to choose from are found in the following table:
Figure 18
– Modes of operation