Toshiba XXXXXXX(<SanSerif1>X/X)
– 31 –
EN
Hydro Unit
Installation Manual
Setting DIP Switches on the Board in Second Remote controller
(option)
• Detach the front cover of the Remoto controller.
• Set the DIP switches on the main board
11
1
Used to activate Hydro Unit back up heaters.
OFF = Back up heaters activated;
ON = back up heaters de-activated
OFF
2
Used to activate hot water cylinder electrical heater.
OFF = hot water cylinder heater activated;
ON = hot water cylinder heater de-activated
OFF
3
Used to activate external booster heater output.
OFF = external booster heater output activated;
ON = external booster heater output de-activated
OFF
4
Not Used
–
–
–
–
–
12
1
Used when a hot water cylinder is connected to
system.
OFF = hot water cylinder connected;
ON = hot water cylinder not connected
OFF
2
Used to activate Zone 1 Operation.
OFF = Zone 1 activated;
ON = Zone 1 de-activated
OFF
3
Used to activate Zone 2 Operation.
OFF = Zone 2 de-activated;
ON = Zone activated
OFF
4
Not Used
–
–
–
–
–
13
1
Used to determine type of 3 way diverting valve
used on system.
OFF = 2 wire/spring return or SPST type valve;
ON = SPDT type valve
OFF
2
Used to activate external boiler output.
OFF = external boiler output de-activated;
ON = external boiler output activated
OFF
3
Used to activate system auto restart after power
failure.
OFF = auto restart activated;
ON = auto restart de-activated
OFF
4
Not Used
–
–
–
–
–
DIP No.
Description
Default
After
Commissioning
Change 1 Change 2 Change 3
1
Used to when a second remote controller is connected
OFF=Header remote control; ON=Second remote
control
OFF
–
–
–
–
2
Used to determine control target when use second
remote controller
OFF=water temperature;
ON;room temperature
OFF
–
–
–
–
3
Not Used
–
–
–
–
–
4
Not Used
–
–
–
–
–
SW No. DIP No.
Description
Default
After
Commissioning
Change 1 Change 2 Change 3
30-EN
+00EF99805101_00Ta.book Page 31 Friday, July 2, 2010 4:36 PM
Summary of Contents for HWS-1403XWHD6-E
Page 47: ... 47 EN Hydro Unit Installation Manual MEMO 46 EN ...
Page 93: ... 93 FR Unité hydroélectrique Manuel d installation NOTES 46 FR ...
Page 139: ... 139 DE Hydrogerät Installationshandbuch NOTIZEN 46 DE ...
Page 185: ... 185 SE Hydroenhet Installationshandbok MEMO 46 SE ...
Page 186: ...EF99805101 ...