Hydro Unit
Installation Manual
• Set DIP SW2 to ON (Room temperature) on the
remote control which you will control the room
temperature with.
DIP SW2 of optional remote control is preset to ON
(Room temperature).
Either one of header or second remote control must
be set as room temperature control.
• To control room temperature instead of water
temperature with this remote control, set function
code “40” of hydro unit to “1”.
8
START UP AND CONFIGURATION
Set the DIP switches and function codes.
Setting DIP Switches on the Board in the Hydro Unit
• Detach the front cover and the electric parts box cover of the Hydro Unit.
• Set the DIP switches on the main board.
ON
OFF
SW10
SW11
SW12
SW13
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
▼
Fig. 8-01
SW No. DIP No.
Description
Default
After
Commissioning
Change 1 Change 2 Change 3
02
1
Boiler install location
OFF = Heating side after 3 way valve
ON = Before 3 way valve
OFF
2
Not Used
–
–
–
–
–
3
Not Used
–
–
–
–
–
4
Used to when an external room thermostat is
connected
OFF = No external room thermostat;
ON = External room thermostat connected
OFF
10
1
P1 Pump operation for hot water
OFF = synchronised with heat pump
ON = Normally run
OFF
2
P1 Pump operation for heating
OFF = Normally run
ON = Stopped at the outside temperature over 20°C
OFF
3
Synchronisation of Pump P2.
OFF = P2 continuous operation(pump off when
remote controller switched off)
ON = P1 synchronised with pump P1
OFF
4
Not Used
–
–
–
–
–
29-EN
+00EF99805101_00Ta.book Page 30 Friday, July 2, 2010 4:36 PM
Summary of Contents for HWS-1403XWHD6-E
Page 47: ... 47 EN Hydro Unit Installation Manual MEMO 46 EN ...
Page 93: ... 93 FR Unité hydroélectrique Manuel d installation NOTES 46 FR ...
Page 139: ... 139 DE Hydrogerät Installationshandbuch NOTIZEN 46 DE ...
Page 185: ... 185 SE Hydroenhet Installationshandbok MEMO 46 SE ...
Page 186: ...EF99805101 ...