TROUBLESHOOTING
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote
controller of the indoor unit are described in the Installation Manual of the Hydro unit.
Verifying current abnormal status
1. Check that DIP switch SW803 is set to OFF.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least 1 second. The LED status changes to display mode 2.
4. Check the code whose display mode 1 equals the LED states jotted down and display mode 2 equals the current
flashing status of LED800 to LED804 from the following table to identify the cause.
Verifying an abnormal state in the past although the abnormal state no longer occurs
1. Set bit 1 of DIP switch SW803 to ON.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least 1 second. The LED status changes to display mode 2.
4. Find an error whose display mode 1 equals the LED states jotted down and display mode 2 equals the current
flashing states of LED800 to LED804 from the following table to identify the error.
• An outside
air temperature (TO) sensor error
can be checked only while it occurs.
No.
Cause
Display mode 1
Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
1
Normal
2
Discharge (TD) sensor error
3
Heat exchanger (TE) sensor error
4
Heat exchanger (TL) sensor error
5
Outside air temperature (TO) sensor error
6
Suction (TS) sensor error
7
Heat sink (TH) sensor error
8
Outdoor temperature sensor (TE/TS) connection error
9
Outdoor EEPROM error
10
Compressor breakdown
11
Compressor lock
12
Current detection circuit error
13
Thermostat for compressor activated
14
Model data not set (on the service P.C. board)
15
MCU-MCU communication error
16
Discharge temperature error
17
Abnormal power (open phase detected or abnormal voltage)
18
Heat sink overheat
19
Gas leak detected
20
4-way valve reverse error
23-EN
Summary of Contents for HWS-1103H-E
Page 29: ... 28 EN Air to Water Heat Pump Installation Manual MEMO 28 EN ...
Page 57: ... 56 Pompe à chaleur air eau Manuel d installation FR NOTES 28 FR ...
Page 85: ... 84 DE Luft Wasser wärmepumpe Installations handbuch NOTIZEN 28 DE ...
Page 113: ... 112 SE Luft till vatten värmepump Installationshandbok MEMO 28 SE ...
Page 114: ...EF99804801 ...