120
GX9 ASD Installation and Operation Manual
BIN Reference Point 1
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
BIN
terminals when the
BIN
terminals are used as the control input while operating in the
Speed
Control
mode.
The discrete input terminals of the
Terminal Board
are used as the
BIN
terminals.
BIN Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
BIN
terminals:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
Binary/BCD
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
• Program
Terminal
Input Terminals
; select and set the desired
discrete input terminals to
Binary Bit
(s)
0 – 7
(or 0 – MSB). The binary
input byte will control the speed of the motor.
• Program
Terminal
Input Terminals
; select and set a discrete input
terminal to
Binary Data Write
. Activation of the
Binary Data Write
terminal will transfer the status of the
Binary Bit
(s)
0 – 7
(or 0 – MSB) to
the control board for speed control.
• Set
BIN Input Point 1 Frequency
• Set the
BIN
value (% of 255
D
) (
) that represents
BIN Input Point 1
Frequency
.
• Set
BIN Input Point 2 Frequency
• Set the
BIN
value (% of 255
D
) (
) that represents
BIN Input Point 2
Frequency
.
• Provide a
Run
command (F and/or R).
Note:
255
D
is the decimal equivalent of the 8-bit BIN byte with all input
terminals set to 1 (255 decimal = 11111111 binary).
Once set, as the
BIN
signal changes are transferred to the control board, the
output frequency of the ASD will vary in accordance with the above settings.
This parameter sets
BIN Reference Point 1
and is entered as 0% to 100% of
the of the range represented by the
BIN
binary input byte 11111111 (255
D
) or
the binary bit(s) 0 – MSB.
Direct Access Number — F228
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
BIN Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the speed of the
BIN
terminals when the
BIN
terminals are used as the control input.
This parameter sets
BIN Input Point 1 Frequency
and is the frequency that is
associated with the setting of
BIN Reference Point 1
.
See
BIN Reference Point 1
(
) for further information on this setting.
Direct Access Number — F229
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -
Max. Freq.
(
Maximum —
Max. Freq.
Units — Hz
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......