GX9 ASD Installation and Operation Manual
121
BIN Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the speed of the
BIN
terminals when the
BIN
terminals are used as the control input.
This parameter sets the
BIN
signal that is associated with
BIN Input Point 2
Frequency
.
This value is entered as 0% to +100% of the
BIN
signal range.
See
BIN Reference Point 1
(
)
for further information on this setting.
Direct Access Number — F230
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
BIN Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the speed of the
BIN
terminals when the
BIN
terminal are used as the control input.
This parameter sets
BIN Input Point 2 Frequency
and is the frequency that is
associated with the setting of
BIN Reference Point 2
.
See
BIN Reference Point 1
(
)
f
or further information on this setting.
Direct Access Number — F231
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — -
Max. Freq.
(
Maximum —
Max. Freq.
Units — Hz
BIN Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
BIN
binary input
terminals when these
terminals are used as the control input while operating in
the
Torque Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a given
BIN
binary input and motor load.
See
for further information on this setting.
This parameter sets
BIN Input Point 1 Torque
and is entered as
-250 to +250% of the rated torque.
Direct Access Number — F232
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
BIN Input Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
BIN
binary input
terminals when these
terminals are used as the control input while operating in
the
Torque Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a given
BIN
binary input and motor load.
See
for further information on this setting.
This parameter sets
BIN Input Point 2 Torque
and is entered as
-250 to +250% of the rated torque.
Direct Access Number — F233
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......