![Toshiba GX9 ASD Quick Start Manual Download Page 27](http://html.mh-extra.com/html/toshiba/gx9-asd/gx9-asd_quick-start-manual_424980027.webp)
GX9 ASD Quick Start Guide
17
Terminal Descriptions
Note:
The programmable terminal assignments may be accessed and changed from the
default settings as mapped on
or via the
Direct Access
method: Program
Direct Access
applicable parameter number
. See the section titled
for the applicable
Direct Access
parameter numbers. For
further information on terminal assignments and default setting changes, see the
sections titled
Default Setting Changes on pg. 53
and
ST
— The default terminal assignment is
Standby
(ST). As the default setting, this terminal must be
activated for normal system operation. The
ST
terminal is activated by connecting
CC
to this terminal
(Sink mode). When deactivated,
OFF
is flashed on the LED screen and the
Not-Ready-to-Run
icon is
displayed on the LCD screen as shown in
. This input terminal may be programmed
to any of the functions listed in the
GX9 ASD Installation & Operation Manual
(see
F113
).
RES
— The default terminal assignment is
Reset
(RES). As the default setting, this terminal resets any
active alarms or faults. The
RES
terminal is activated by connecting
CC
to this terminal (Sink mode). A
momentary connection to
CC
resets the ASD and any fault indications from the display.
Reset
is
effective when faulted only. This input terminal may be programmed to any of the functions listed in the
GX9 ASD Installation & Operation Manual
(see
F114
). The cause of the trip must be corrected for a
Reset
to enable the system for normal ASD operations.
F
— The default terminal assignment is
Forward
(F) run. As the default setting, this terminal provides
a forward run command. The
F
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in the
GX9 ASD Installation & Operation
Manual
(see
F111
).
R
— The default terminal assignment is
Reverse
(R) run. As the default setting, this terminal provides
a reverse run command. The
R
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in the
GX9 ASD Installation & Operation
Manual
(see
F112
).
S1
— The default terminal assignment is
Preset Speed 1
(S1). As the default setting, this terminal
provides a run command for the
Preset Speed 1
setting (
F018
). The
S1
terminal is activated by
connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 1
run
command for the duration of the activation. This input terminal may be programmed to any of the
functions listed in the
GX9 ASD Installation & Operation Manual
(see
F115
).
S2
— The default terminal assignment is
Preset Speed 2
(S2). As the default setting, this terminal
provides a run command for the
Preset Speed 2
setting (
F019
). The
S2
terminal is activated by
connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 2
run
command for the duration of the activation. This input terminal may be programmed to any of the
functions listed in the
GX9 ASD Installation & Operation Manual
(see
F116
).
S3
— The default terminal assignment is
Preset Speed 3
(S3). As the default setting, this terminal
provides a run command for the
Preset Speed 3
setting (
F020
). The
S3
terminal is activated by
connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 3
run
command for the duration of the activation. This input terminal may be programmed to any of the
functions listed in the
GX9 ASD Installation & Operation Manual
(see
F117
).
S4
— The default terminal assignment is
Emergency Off
(S4). As the default setting, this terminal
provides an
Emergency Off
command upon activation and the system remains in the
Emergency Off
condition until reset. The
S4
terminal is activated by connecting
CC
to this terminal (Sink mode). This
input terminal may be programmed to any of the functions listed in the
GX9 ASD Installation &
Operation Manual
(see
F118
).
Summary of Contents for GX9 ASD
Page 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Page 2: ......
Page 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Page 4: ......
Page 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Page 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Page 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Page 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Page 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Page 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Page 99: ......