GX9 ASD Quick Start Guide
9
System Setup Requirements
•
When using the ASD as an integral part of a larger system, it is the responsibility of the ASD
installer/maintenance personnel to ensure that there is a fail-safe in place (i.e., an arrangement
designed to switch the system to a safe condition if there is a fault or failure).
•
Power factor improvement capacitors or surge absorbers
MUST NOT
be installed on the three-
phase output of the ASD.
•
Use of the built-in system protective features is highly recommended (i.e., Emergency Off,
Overload Protection, etc.).
•
The operating controls and system status indicators shall be clearly readable and positioned where
they may be viewed without obstruction.
•
Additional warnings and notifications shall be posted at the equipment installation location as
deemed required by
.
•
System safety features shall be employed and designed into the integrated system in a manner such
that system operation, even in the event of system failure, will not cause harm or result in system
damage or injury to personnel (i.e., Emergency Off, Auto-Restart settings, System Interlocks, etc.).
•
The programming setup and system configuration of the ASD may allow it to start the motor
unexpectedly. A familiarity with the
Auto-Restart
and
Retry
settings is a requirement to use this
product.
•
The setup procedures included within this guide may require a
Reset
before performing the
procedure. Application-specific settings may then be performed. The pre-Reset conditions may be
saved (see
F007
).
•
There may be thermal or physical properties, or ancillary devices integrated into the overall system
that may allow for the ASD to start the motor without warning. Warning signs to this effect must be
clearly posted at or near the machinery/hazard.
•
If a secondary magnetic contactor (MC) or an ASD output disconnect is used between the ASD and
the load, it should be interlocked to halt the ASD before the secondary contact opens. If the output
contactor is used for bypass operation, it must be interlocked such that commercial power is never
applied to the ASD output terminals (U, V, or W).
•
When using an ASD output disconnect, the ASD and the motor must be stopped before the
disconnect is either opened or closed. Closing the output disconnect while the 3-phase output of the
ASD is active may result in equipment damage or injury to personnel.
CAUTION
Summary of Contents for GX9 ASD
Page 1: ...GX9 ASD Quick Start Guide TOSHIBA GX9 ASD Quick Start Guide DN 66900 001 March 2014 ...
Page 2: ......
Page 3: ...Document Number 66900 001 March 2014 GX9 ASD Quick Start Guide ...
Page 4: ......
Page 88: ...78 GX9 ASD Quick Start Guide Figure 33 GX9 ASD 5 0 20 HP Enclosure ...
Page 89: ...GX9 ASD Quick Start Guide 79 Figure 34 GX9 ASD 25 75 HP Enclosure ...
Page 90: ...80 GX9 ASD Quick Start Guide Figure 35 GX9 ASD 100 200 HP Enclosure ...
Page 91: ...GX9 ASD Quick Start Guide 81 Figure 36 GX9 ASD 250 400 HP Enclosure ...
Page 92: ...82 GX9 ASD Quick Start Guide Figure 37 GX9 ASD 500 800 HP Enclosure ...
Page 93: ...GX9 ASD Quick Start Guide 83 Figure 38 GX9 ASD 900 1200 HP Enclosure ...
Page 99: ......